EasyGrid LT User Guide
25
Power
5.2
Terminal block: Phoenix Contact # 1827635.
Wire gage: 22 to 14 AWG (0.33 to 1.5mm
2
)
Recommended strip length: 7mm
Screw driver blade recommendation: 0.4 x 2.5mm (0.23Nm torque recommendation)
CAUTION
When you chose the power supply, make sure to check the temperature derating in order to have 15W
available for all the working temperature.
Power supply:
The EasyGrid LT has the following power requirement:
•
Voltage: 24 Vdc ± 5%
•
Power consumption: 15 Watts
FISO recommends the use of Power Supply # 2868648 from Phoenix Contact.
System Ground:
8 AWG (8mm2) copper conductors required for grounding the EasyGrid LT for electromagnetic
interference (EMI) purposes. FISO recommends Earth strap AMP# 1337670-3 or Crimp terminal AMP ring
tongue terminal # 8-33460-2. M5 nut Torque recommendation for system ground is 2Nm (18lb-in).