EasyGrid LT User Guide
6
Grounding Terminal
4.3
This terminal provides an additional level of immunity against electromagnetic
interferences. It should always be grounded trough a low inductive conductor
(we suggest multiple braid 8 AWG copper wire) to insure adequate protection.
Powering the
EasyGrid LT
4.4
The EasyGrid LT requires a
24 volts DC
supply.
The power input terminal block is located on the top left of the terminal panel of the unit.
1.
Make sure that power is off when connecting the power supply to the unit.
2.
Connect the unit to the power supply using terminal block connectors V+, V-.
3.
Wire the power input terminal block to a power supply providing the required voltage and
power.
4.
To power ON, press the
I
on the switch. To power OFF, press the
O
on the switch.
Please refer to the power supply operating guide for important notices and installation information.
WARNING
To avoid damage to the unit, make sure that the power fed into the input complies with
technical specifications. No other voltage level or range is accepted.
Power Input
Label
Description
V+
V-
ON/OFF Switch