Figure 11. RS485 Installation Guidelines

100 OHM RESISTOR

A6798 / IL

Figure 12. M1000 Series RS232 to RS485 

ConverterBack Panel

W6490/IL

the RS485 input. (The connection labeled RS485 IN is
only used when the unit is installed as a repeater.)

The set of ten switches near the center of the

back panel determine the converter baud rate.

The set of three switches near the RS485 OUT

connector determine the termination and biasing of the
RS485 output.

For the set of three switches adjacent to the RS485
connectors, when in the up position the switch labeled
1K places a 1k ohm pull-up resistor between the

DATA+ line and +5 Vdc. Placing the switch labeled
–1K in the up position connects a 1k ohm pull-down
resistor between the DATA– line and ground. Placing
the switch labeled 220 in the up position terminates
the RS485 input or output with a 220 ohm resistor.

For additional information on setting the converter DIP
switches, refer to the converter instruction manual.

Note

Do not use a pencil to set the switches.
Graphite from the pencil can fall into the
switches causing them to fail.

To set the switches, use a pointed object to push the
switch to the desired position.

Setting the Converter RS485 Termination
and Biasing

When the converter is used as an RS232-to-RS485
converter, set the three switches adjacent to the
RS485 IN connector as follows: set the switches la-
beled +1K and –1K to the up position and the switch
labeled 220 to the down position. When using the unit
as a repeater place all three switches in the up posi-
tion.

Содержание HART 2530H1

Страница 1: ...1 Connecting Field Devices to the Multiplexer Using the Type HJ200 Junction Box without HART Filters 12 Connecting a HART Communicator Using the Type HJ200 Junction Box 12 System Startup 12 Verifying...

Страница 2: ...5 DIN46277 or T type EN50022 DIN46277 3 DIN rail Dis tance from RS232 to RS485 converter is 3000 feet 914 m maximum longer distances are possible with an RS485 repeater Dimensions 14 2 in 360 mm long...

Страница 3: ...nicates to the multiplexer network through a serial port using RS232 signal levels Therefore a converter is required to convert the RS232 signal to an RS485 sig nal Typically the multiplexer is insta...

Страница 4: ...ccepts up to 16 filter or field device connections Specifications Specifications for the Type 2530H1 HART interchange multiplexer are listed in table 1 Specifications for the Type HJ200 junction box a...

Страница 5: ...es HART Filters Instruction Manual WARNING To avoid personal injury or property damage from an uncontrolled process Figure 7 Type HF210 HART Filter Showing Normal Polarity Orientation CONTROL SYSTEM C...

Страница 6: ...rminal cage clamp style connectors for the filter input filter Figure 9 Type HJ200 Junction Box Printed Wiring Board Removal APPLY PRESSURE TO WALLS OF MOUNTING TRACK TO REMOVE PRINTED WIRING BOARD W6...

Страница 7: ...nd B terminal of the next unit i e A to A and B to B 2 Place a 100 ohm resistor between the A and B ter minals on the last multiplexer in the arrangement Note The following step is optional 3 Connect...

Страница 8: ...up position connects a 1k ohm pull down resistor between the DATA line and ground Placing the switch labeled 220 in the up position terminates the RS485 input or output with a 220 ohm resistor For ad...

Страница 9: ...network address es There are a total of 32 possible addresses 0 through 31 for assignment to the multiplexer Each multiplexer in an RS485 network must have a different address When setting an address...

Страница 10: ...UTION To avoid HART communication failure do not use more than one of the above methods to connect a single field device to the same multiplexer Connecting HART Filters Directly to the Multiplexer For...

Страница 11: ...connec tor on the multiplexer labeled LOOPS 1 16 Channel numbers 17 through 32 designate the channel number Figure 16 Junction Box Printed Wiring Board Show ing HART Communication Channel Identificat...

Страница 12: ...eld device with the handheld HART communicator To use the junction box as a connection point for a HART communicator 1 Mount the junction box as described in the Installa tion section 2 Connect the fi...

Страница 13: ...er Addresses Note After changing the multiplexer switch positions power to the multiplexer must be removed and reapplied before the change will become effective There are 32 available addresses for th...

Страница 14: ...the off position d Remove power from the multiplexer e Re apply power to the multiplexer All three LEDs flashing together indicate a seri ous fault Return the unit for service All three LEDs lit cont...

Отзывы: