background image

Type 2530H1

14

The amber POWER ON LED is continuously lit.

The green RUN LED flashes during initialization

after power application or while the host computer is
scanning the multiplexer.

The red FAULT LED lights momentarily during

initialization and when a fault is detected.

After power application and on command from the
host computer, the HART interchange multiplexer per-
forms a self-test. After the test is complete, the config-
uration of the lights will indicate if a fault exists:

None of the LEDs lit indicates no power or low

voltage

If all LEDs flash in sequence, the HART inter-

change multiplexer is in test mode. To remove the unit
from test mode:

c.  Move DIP switch eight to the off position.

d.  Remove power from the multiplexer.

e.  Re-apply power to the multiplexer

All three LEDs flashing together indicate a seri-

ous fault. Return the unit for service.

All three LEDs lit continuously indicates a serious

fault. Return the unit for service.

Figure 18. HART Interchange Multiplexer LED Indicators

W6485/IL

FAULT

RED

POWER ON

AMBER

RUN

GREEN

Service

Service support for the HART interchange multiplexer,
cabling, and configuration software is obtained through
your local Fisher-Rosemount Service Center. Contact
the Fisher-Rosemount office in your area for the loca-
tion of the nearest service center.

For questions about HART interchange multiplexers,
call the Fisher-Rosemount National Response Center
at 800-654-7768.

For information, contact Fisher Controls:
Marshalltown, Iowa 50158 USA
Cernay 68700 France 
Sao Paulo 05424 Brazil
Singapore 0512

                                   

                                        

 

Printed in U.S.A.

Содержание HART 2530H1

Страница 1: ...1 Connecting Field Devices to the Multiplexer Using the Type HJ200 Junction Box without HART Filters 12 Connecting a HART Communicator Using the Type HJ200 Junction Box 12 System Startup 12 Verifying...

Страница 2: ...5 DIN46277 or T type EN50022 DIN46277 3 DIN rail Dis tance from RS232 to RS485 converter is 3000 feet 914 m maximum longer distances are possible with an RS485 repeater Dimensions 14 2 in 360 mm long...

Страница 3: ...nicates to the multiplexer network through a serial port using RS232 signal levels Therefore a converter is required to convert the RS232 signal to an RS485 sig nal Typically the multiplexer is insta...

Страница 4: ...ccepts up to 16 filter or field device connections Specifications Specifications for the Type 2530H1 HART interchange multiplexer are listed in table 1 Specifications for the Type HJ200 junction box a...

Страница 5: ...es HART Filters Instruction Manual WARNING To avoid personal injury or property damage from an uncontrolled process Figure 7 Type HF210 HART Filter Showing Normal Polarity Orientation CONTROL SYSTEM C...

Страница 6: ...rminal cage clamp style connectors for the filter input filter Figure 9 Type HJ200 Junction Box Printed Wiring Board Removal APPLY PRESSURE TO WALLS OF MOUNTING TRACK TO REMOVE PRINTED WIRING BOARD W6...

Страница 7: ...nd B terminal of the next unit i e A to A and B to B 2 Place a 100 ohm resistor between the A and B ter minals on the last multiplexer in the arrangement Note The following step is optional 3 Connect...

Страница 8: ...up position connects a 1k ohm pull down resistor between the DATA line and ground Placing the switch labeled 220 in the up position terminates the RS485 input or output with a 220 ohm resistor For ad...

Страница 9: ...network address es There are a total of 32 possible addresses 0 through 31 for assignment to the multiplexer Each multiplexer in an RS485 network must have a different address When setting an address...

Страница 10: ...UTION To avoid HART communication failure do not use more than one of the above methods to connect a single field device to the same multiplexer Connecting HART Filters Directly to the Multiplexer For...

Страница 11: ...connec tor on the multiplexer labeled LOOPS 1 16 Channel numbers 17 through 32 designate the channel number Figure 16 Junction Box Printed Wiring Board Show ing HART Communication Channel Identificat...

Страница 12: ...eld device with the handheld HART communicator To use the junction box as a connection point for a HART communicator 1 Mount the junction box as described in the Installa tion section 2 Connect the fi...

Страница 13: ...er Addresses Note After changing the multiplexer switch positions power to the multiplexer must be removed and reapplied before the change will become effective There are 32 available addresses for th...

Страница 14: ...the off position d Remove power from the multiplexer e Re apply power to the multiplexer All three LEDs flashing together indicate a seri ous fault Return the unit for service All three LEDs lit cont...

Отзывы: