Fisher HART 2530H1 Скачать руководство пользователя страница 13

Type 2530H1

13

Verifying the Network Baud Rate

Note

After changing the switch positions on
the multiplexer or RS232-to-RS485 con-
verter, power to the device must be re-
moved and reapplied before the change
will become effective.

The HART interchange multiplexers, RS232-to-RS485
converter, and the ValveLink software all must com-
municate at the same rate for the network to function
properly. Setting the baud rate at 38.4K baud provides
the maximum data update rate.

The RS232-to-RS485 converter and HART inter-
change multiplexer are preset for a baud rate of 19.2k
baud. To select a 38.4k baud rate or to verify the
switch settings, refer to the appropriate switch setting
paragraph in the Installation section of this manual.

To verify the baud rate of the ValveLink software:

1.  Start up the software by double clicking on the Val-
veLink icon.

2.  At the logon display, enter a username and pass-
word for a user that has access to preferences.

3.  From the menu bar, select Setup. Select Prefer-
ences from the menu.

4.  If the Comm Ports page is not displayed, click on
the Comm Ports tab to display the page.

5.  Select the one or two comm ports that have the
converters and multiplexers connected to them by
placing an X in the check box. Place an X in a check
box by clicking on the check box. To remove an X in a
check box, click on the check box to turn the X off.

6.  Select either 9600 baud, 19.2k baud or 38.4k baud
by clicking on the appropriate option button. The 38.4K
baud selection is recommended.

7.  Click on the Save button to save all selections. To
make these selections effective, exit the ValveLink
software and restart the application.

Verifying the HART Interchange
Multiplexer Addresses

Note

After changing the multiplexer switch
positions, power to the multiplexer must
be removed and reapplied before the
change will become effective.

There are 32 available addresses for the HART inter-
change multiplexer, 0 through 31. Be sure no two mul-

Figure 17. M1000 Series RS232 to RS485 Converter Front

Panel Showing LED Indicators and Power Switch

W6482/IL

tiplexers have the same address. To verify the multi-
plexer addresses:

1.  Remove power from the multiplexer.

2.  Verify the addresses by comparing the settings of
switches 1 through 5 with the settings listed in table 3.
Make any necessary changes to the switch settings.

3.  Apply power to the multiplexer.

Verifying the RS485 Network

The RS485 network must be less than 3000 feet
(914.4 m) if one RS232-to-RS485 converter is used. If
the network is greater than 3000 feet (914.4 m), a se-
cond converter can be used as a repeater. Refer to
the converter manual for information on using the con-
verter as a repeater.

Be sure a 100 ohm resistor is connected across the A
and B terminals of the last multiplexer in the network.

Reading the Converter LED Indicators

The RS232-to-RS485 converter has three LEDs on
the front panel as shown in figure 17. In normal opera-
tion the LED configuration is as follows:

The LED labeled POWER is normally on indicat-

ing adequate power supply voltage is applied to the
converter.

The LED labeled TRANSMIT illuminates as data

is transmitted from the host computer onto the RS485
network. This LED will vary in intensity as the comput-
er communicates over the network.

The LED labeled FAULT illuminates if excessive

current is being drawn from the in24 Vdc, 1
Amp power supply. This LED should normally be off.

Reading the Multiplexer LED Indicators

The HART interchange multiplexer has three LEDs as
shown in figure 18. In normal operation the LED con-
figuration is as follows:

Содержание HART 2530H1

Страница 1: ...1 Connecting Field Devices to the Multiplexer Using the Type HJ200 Junction Box without HART Filters 12 Connecting a HART Communicator Using the Type HJ200 Junction Box 12 System Startup 12 Verifying...

Страница 2: ...5 DIN46277 or T type EN50022 DIN46277 3 DIN rail Dis tance from RS232 to RS485 converter is 3000 feet 914 m maximum longer distances are possible with an RS485 repeater Dimensions 14 2 in 360 mm long...

Страница 3: ...nicates to the multiplexer network through a serial port using RS232 signal levels Therefore a converter is required to convert the RS232 signal to an RS485 sig nal Typically the multiplexer is insta...

Страница 4: ...ccepts up to 16 filter or field device connections Specifications Specifications for the Type 2530H1 HART interchange multiplexer are listed in table 1 Specifications for the Type HJ200 junction box a...

Страница 5: ...es HART Filters Instruction Manual WARNING To avoid personal injury or property damage from an uncontrolled process Figure 7 Type HF210 HART Filter Showing Normal Polarity Orientation CONTROL SYSTEM C...

Страница 6: ...rminal cage clamp style connectors for the filter input filter Figure 9 Type HJ200 Junction Box Printed Wiring Board Removal APPLY PRESSURE TO WALLS OF MOUNTING TRACK TO REMOVE PRINTED WIRING BOARD W6...

Страница 7: ...nd B terminal of the next unit i e A to A and B to B 2 Place a 100 ohm resistor between the A and B ter minals on the last multiplexer in the arrangement Note The following step is optional 3 Connect...

Страница 8: ...up position connects a 1k ohm pull down resistor between the DATA line and ground Placing the switch labeled 220 in the up position terminates the RS485 input or output with a 220 ohm resistor For ad...

Страница 9: ...network address es There are a total of 32 possible addresses 0 through 31 for assignment to the multiplexer Each multiplexer in an RS485 network must have a different address When setting an address...

Страница 10: ...UTION To avoid HART communication failure do not use more than one of the above methods to connect a single field device to the same multiplexer Connecting HART Filters Directly to the Multiplexer For...

Страница 11: ...connec tor on the multiplexer labeled LOOPS 1 16 Channel numbers 17 through 32 designate the channel number Figure 16 Junction Box Printed Wiring Board Show ing HART Communication Channel Identificat...

Страница 12: ...eld device with the handheld HART communicator To use the junction box as a connection point for a HART communicator 1 Mount the junction box as described in the Installa tion section 2 Connect the fi...

Страница 13: ...er Addresses Note After changing the multiplexer switch positions power to the multiplexer must be removed and reapplied before the change will become effective There are 32 available addresses for th...

Страница 14: ...the off position d Remove power from the multiplexer e Re apply power to the multiplexer All three LEDs flashing together indicate a seri ous fault Return the unit for service All three LEDs lit cont...

Отзывы: