Appendix
29.12.04
Panda AGT-DC 4000 PVMV-N s00670 - Chapter F: Appendix Page V
MOTOR TURNS OVER BUT DOES NOT START
Cause
Solution
Stop solenoid valve not opening.
Check wire connections and circuitry to solenoid valve.
ref. DC wiring diagram: Relay K2, Fuse)
Fuel pump does not operate.
Check fuel-filter and pump: clean if necessary.
Lack of fuel.
Check fuel supply.
Glow-plugs not working correctly.
Check glow plugs and heating time.
Too much air in fuel lines.
Test fuel system for leakage. Bleed air from fuel
system (refer to section "Air-bleeding of the Fuel
System").
Fuel filter blocked.
Replace fuel filter.
Low compression pressure.
See Kubota motor-manual.
MOTOR DOES NOT TURN OVER AT THE NORMAL SPEED DURING THE STARTING PROCESS
Cause
Solution
Starter battery voltage insufficient.
Check battery.
Damaged bearing(s) piston (seized).
Repairs need to be carried out by Kubota-Service.
(refer to Kubota motor-manual)
Cooling water in combustion chamber.
1. Turn generator "OFF" at control panel.
2. Remove the glow plug (see Kubota-manual).
3. Rotate the motor by hand carefully.
4. Check if there is water in the oil and change both oil
and filter if necessary.
5. Determine cause for excess water in the combus
tion chamber. The excess water can be caused by a
defective air vent in the cooling water system, which
should be checked and cleaned, or replaced if
faulty.
MOTOR RUNS IRREGULARLY
Cause
Solution
Faulty centrifugal injector governor.
Have the centrifugal governor inspected by a Kubota-
Service technician.
Too much air in fuel lines.
Bleed air from fuel system.
Содержание AGT 4000 PVMV-N
Страница 36: ...The Panda Generator Page 30 Panda AGT DC 4000 PVMV N s00670 Chapter A The Panda Generator 29 12 04...
Страница 52: ...Maintenance Instructions Page 46 Panda AGT DC 4000 PVMV N s00670 Chapter C Maintenance Instructions 29 12 04...
Страница 64: ...Generator Failure Page 58 Panda AGT DC 4000 PVMV N s00670 Chapter D Generator Failure 29 12 04...
Страница 82: ...Installation Instructions Page 76 Panda AGT DC 4000 PVMV N s00670 Chapter E Installation Instructions 29 12 04...
Страница 90: ...Appendix Page VIII Panda AGT DC 4000 PVMV N s00670 Chapter F Appendix 29 12 04...
Страница 93: ...Measurements 29 12 04 Panda AGT DC 4000 PVMV N s00670 Chapter F Appendix Page XI F 6 Measurements...
Страница 94: ...Measurements Page XII Panda AGT DC 4000 PVMV N s00670 Chapter F Appendix 29 12 04...