Maintenance Instructions
Seite/Page 116 - Kaptitel/Chapter 9: Maintenance Instructions
9.12.14
9.9.1.3 Check electrolyte density
Fig. 9.9.1.3-1: Battery
• Measure the electrolyte density of individual cells with a
commercial hydrometer. The hydrometer reading (see table
on following page) indicates the battery’s state of charge.
During measurement, the temperature of the electrolyte
should preferably be 20 °C.
Attention
The gases emitted by the battery are explosive! Keep
sparks and naked flames away from the battery!
Do not allow battery acid to come into contact with skin
or clothing!
Wear protective goggles!
Do not rest tools on the battery!
9.10 Grease lubricated generator backend bearing
A bearing change should only be executed by a trained expert.
The bearing is, depending on the generator model, equipped with a black cooling disc.
The grease lubricated generator bearing is maintenance free over its durability, but should be exchanged every
1500 operating hours.
Electrolyte density
in [kg/ l]
Charge status
Normal
Tropical
1.28
1.23
well charged
1.20
1.12
semi-charged, re-charge
1.12
1.08
discharged, immediately charge
Содержание 10000/9
Страница 10: ...Seite Page 10 Kapitel Chapter 2 9 12 14 Leere Seite Intentionally blank...
Страница 62: ...The Panda Generator Seite Page 62 Kaptitel Chapter 6 The Panda Generator 9 12 14...
Страница 220: ...Tables Seite Page 220 Kaptitel Chapter 11 Tables 9 12 14...
Страница 244: ...Seite Page 244 Kapitel Chapter 13 General operation 9 12 14 Leere Seite Intentionally blank General operation...
Страница 246: ...Seite Page 246 Kapitel Chapter 14 Measurements 9 12 14 Leere Seite Intentionally blank Measurements...