APPENDIX No 2

 

 

Proper position of the SureFire II™ SP-32 and SP-48 Pilots on burners 

Appendix shows a sample of typical positions of gas pilots on two types of burners. 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. A

  Typical for power & utility boilers, industrial heaters -  shows position of  

SP-32

 and 

SP-48

 Gas Igniter operating 

as an intermittent (light-off) on a sample single gun main burner, oil or gas fired, vertical or horizontal mounting. 

The pilot air tube tip can reach the swirler or can be placed before it. Pilot tip cannot extend beyond the swirler plane. 

 

Fig. B

  Typical for refinery, petrochem and industrial heaters - shows position of  

SP-32

 and 

SP-48

 Gas Igniter operating 

as a continuous pilot on a sample main burner, with gas spuds and central oil or gas gun, vertical mounting.  

The pilot air tube tip can be mounted in the throat or in the swirler. Pilot tip cannot extend beyond the heater lining or 
swirler plane and has to be at least 150 mm away from the main burner nozzle flame. 

 

 

WARNING: PILOT TIP CANNOT BE MOUNTED IN MAIN BURNER FLAME. THE 
DISTANCE SHOULD BE AT LEAST 150 MM FROM THE FUEL CONE. PILOT TIP 
CANNOT EXTEND BEYOND THE HEATER LINING OR BURNER THROAT. 

 

 

WARNING: IN CASE OF ANY DOUBTS CONCERNING THE PILOT POSITION ON 
A BURNER CONSULT PILOT AND MAIN BURNER MANUFACTURERS.

 

 

 

Atomized fuel cone

Incorrect position
too close to flame

Correct position

SP-32, -48 Gas Pilot

Gas spuds

Oil or gas central gun

 

FIGURE  

 B

 

Atomized fuel cone

Incorrect position
too close to flame

Correct position

SP-32, -48 Gas Igniter

Oil or gas gun

 

FIGURE  

 A

 

Содержание SureFire II SP-48-NG-FD

Страница 1: ...d each unit is checked and tested before dispatch Acquaintance with the following instructions and strict attention to the indications reduce the possibility of equipment failure to a minimum and ensu...

Страница 2: ...xits the main nozzle at the outlet of the air tube The main flame then stabilizes in the primary combustion zone at the outlet of the air tube The swirler stabilizer plate and holes in air tube provid...

Страница 3: ...he Fireye High Tension Igniter the end of the rod tip should be placed at a distance of 10 mm back from the swirler stabilizer see Fig 1 In case of the High Energy Spark Igniter the rod tip should be...

Страница 4: ...ling the pilot burner please follow the rules below 6 1 Use pilot only for its intended purpose 6 2 At the time of installation operation and maintenance follow the procedures described in the instruc...

Страница 5: ...he burner plate with a diameter slightly larger than the diameter of the mounting tube b The mounting tube for welding slide the mounting tube in the hole and set it in the correct position insertion...

Страница 6: ...tors may be used c To ensure a long and trouble free operation of the pilot it should be kept clean Check the condition of the gas pipe and if the orifices are not blocked Remove all buildups Hoses sh...

Страница 7: ...flame stabilizes at the end of the air tube and reaches a blue yellow color If the airflow is too low the end of the air tube may start to glow it starts to glow at 400 500 C as the main flame burns i...

Страница 8: ...the flame after trial for ignition the valves are closed and electrical igniter is switched off i Eventual repeating of trial for ignition sequence depends on the application Details of sequence timin...

Страница 9: ...does not operate correctly check the following a All manual gas valves on gas supply line were open and there is gas available b All valves in the supply line are functioning properly c The preset gas...

Страница 10: ...intenance of igniter contrary to the instructions in the user manual unauthorized igniter modifications or repairs made by unauthorized personnel use of components or spare parts other than original 1...

Страница 11: ...ght 3 0 m ins length The Table 2 below shows Part Numbers of gas igniter mounting tubes and spare parts Table 2 SureFire II Pilot Mounting Tubes Spare Parts Part No Description SP 48 MTF Mounting Tube...

Страница 12: ...12 APPENDIX No 1 The Pilot capacity vs gas pressure graphs standard version Remark The real measured capacity may differ by 5 depending on a particular pilot and measurement conditions...

Страница 13: ...us pilot on a sample main burner with gas spuds and central oil or gas gun vertical mounting The pilot air tube tip can be mounted in the throat or in the swirler Pilot tip cannot extend beyond the he...

Страница 14: ...nd especially refinery gas Refinery Off Gas needs additional engineering and testing because their gas compositions and calorific values are different than these of NG PG and LPG taken for gas pilot d...

Страница 15: ...5 cubic foot ft3 Air flow rate 1 cubic metre hour m3 h x 0 589 standard cubic foot min SCFM Weight 1 kilogram kg x 2 2046 pound lb Pressure 1 kilopascal kPa x 6 895 pound square inch gauge psig x 4 01...

Страница 16: ...is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND...

Отзывы: