background image

6

 

®

 

 

  

 

 

 

 

 

 

 

c)   Gas part assembly and air tube should be fastened by the mounting ring thread joint. Ensure that the ring 

gasket is correctly fitted in the gas head seat (see Fig. 4). 

d)   The complete pilot (air tube) can be inserted into the mounting tube. In order to make the air tube slide-in 

easier, apply a small amount of high temperature resistant grease. 

e)    The insertion depth of 

SP-48-FD

 pilot is determined by the design of the main burner. If an existing pilot 

has to be replaced, the insertion length and pilot tip position should be the same. In case of any doubts, the 
position of the pilot should be consulted with the pilot and burner manufacturer. 

f) 

After  determining  the  position  of  the  complete  pilot  relative  to  the  mounting  tube,  the  mounting  tube 
clamping screws should be tightened to prevent the device from moving. 

 

FIGURE 4. 

Gas head with ring gasket and swirler-stabilizer assembly with bleed and main gas orifices

 

 

 

 
 
 

 
 
 
 

 
 
 

 
 
 

 

 

7.3  GAS AND AIR SUPPLY INSTALLATION

 

a)    The  pilot  must  be  set  in  the  mounting  tube  such  that  the  air  and  gas  connections  are  in  the  desired 

positions.

 

b)    Connect  the  air  and  gas  hoses  to  the  appropriate  pilot  inputs.  Hoses  cannot  be  tangled  or  twisted.  

If necessary, additional connectors may be used.

 

c)    To ensure a long and trouble-free operation of the pilot it should be kept clean. Check the condition of the 

gas pipe and if the orifices are not blocked. Remove all buildups. Hoses should be dry and not cracked.

 

d)   During  maintenance or service works, secure the disconnected ends of the hoses by closing the ends with 

a plug or a tape.

 

e)    Use the automatic shutoff valves of the 

appropriate size and the respective closing rate and pilot gas pressure 

measurement with safety interlocks (compliant with the  requirements of  relevant standards concerning the 
shut-off safety fuel valves and burner safety) to be sure that the gas delivered to the pilot is of an adequate 
pressure and can be quickly and 

effectively shut off.

 

f)    Use  manual shut-off valves on air and gas lines for  each pilot  in case of  maintenance or replacement and 

for adjustment of pressure and flow on each pilot separately.

 

 

 

REMARK

:  AT  THE  DESIGN  STAGE  DETERMINE  LENGTH  OF  CABLES  AND 

FLEXIBLE  AIR  AND  GAS  CONNECTIONS  TO  ACCOMMODATE  ANY  EXPECTED 
HEATER OR BOILER CONSTRUCTION MOVEMENT

 

 

 

7.4  CABLING

 

Wiring  and  electrical connections design  and  layout  should  be  in  accordance with  the  requirements  for burner 
installation devices specified in their instructions and the relevant regulations.

 

 

 

Ring  gasket 

HTI rod tip  

Bracket 

Gas divider with main orifice 

Main orifice gas tube 

Bleed gas orifice 

Swirler- stabilizer plate 

Содержание SureFire II SP-48-NG-FD

Страница 1: ...d each unit is checked and tested before dispatch Acquaintance with the following instructions and strict attention to the indications reduce the possibility of equipment failure to a minimum and ensu...

Страница 2: ...xits the main nozzle at the outlet of the air tube The main flame then stabilizes in the primary combustion zone at the outlet of the air tube The swirler stabilizer plate and holes in air tube provid...

Страница 3: ...he Fireye High Tension Igniter the end of the rod tip should be placed at a distance of 10 mm back from the swirler stabilizer see Fig 1 In case of the High Energy Spark Igniter the rod tip should be...

Страница 4: ...ling the pilot burner please follow the rules below 6 1 Use pilot only for its intended purpose 6 2 At the time of installation operation and maintenance follow the procedures described in the instruc...

Страница 5: ...he burner plate with a diameter slightly larger than the diameter of the mounting tube b The mounting tube for welding slide the mounting tube in the hole and set it in the correct position insertion...

Страница 6: ...tors may be used c To ensure a long and trouble free operation of the pilot it should be kept clean Check the condition of the gas pipe and if the orifices are not blocked Remove all buildups Hoses sh...

Страница 7: ...flame stabilizes at the end of the air tube and reaches a blue yellow color If the airflow is too low the end of the air tube may start to glow it starts to glow at 400 500 C as the main flame burns i...

Страница 8: ...the flame after trial for ignition the valves are closed and electrical igniter is switched off i Eventual repeating of trial for ignition sequence depends on the application Details of sequence timin...

Страница 9: ...does not operate correctly check the following a All manual gas valves on gas supply line were open and there is gas available b All valves in the supply line are functioning properly c The preset gas...

Страница 10: ...intenance of igniter contrary to the instructions in the user manual unauthorized igniter modifications or repairs made by unauthorized personnel use of components or spare parts other than original 1...

Страница 11: ...ght 3 0 m ins length The Table 2 below shows Part Numbers of gas igniter mounting tubes and spare parts Table 2 SureFire II Pilot Mounting Tubes Spare Parts Part No Description SP 48 MTF Mounting Tube...

Страница 12: ...12 APPENDIX No 1 The Pilot capacity vs gas pressure graphs standard version Remark The real measured capacity may differ by 5 depending on a particular pilot and measurement conditions...

Страница 13: ...us pilot on a sample main burner with gas spuds and central oil or gas gun vertical mounting The pilot air tube tip can be mounted in the throat or in the swirler Pilot tip cannot extend beyond the he...

Страница 14: ...nd especially refinery gas Refinery Off Gas needs additional engineering and testing because their gas compositions and calorific values are different than these of NG PG and LPG taken for gas pilot d...

Страница 15: ...5 cubic foot ft3 Air flow rate 1 cubic metre hour m3 h x 0 589 standard cubic foot min SCFM Weight 1 kilogram kg x 2 2046 pound lb Pressure 1 kilopascal kPa x 6 895 pound square inch gauge psig x 4 01...

Страница 16: ...is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND...

Отзывы: