30
®
Table 1- Message Table
DEC
HEX
E110 FLAME-MONITOR MESSAGES
1
1
R
L1-13 OPEN
2
2
H
HOLD FALSE FLAME- STANDBY
3
3
R
LOW FIRE PURGE
4
4
H
HOLD D-8 LIMIT OPEN- PURGE
5
5
H
HOLD 3-P AIR FLOW OPEN
6
6
L
LOCKOUT LINE FREQUENCY NOISE DETECTED
7
7
L
LOCKOUT FLAME FAIL - PTFI
8
8
C
CHECK UNIT ADDRESS
9
9
H
HOLD M-D LIMIT OPEN
10
A
R
IGNITION TIMING - PTFI
11
B
12
C
R
FLAME SIGNAL - AUTO
13
D
R
CYCLE COMPLETE - POST PURGE
14
E
R
L1-13 OPEN (AFTER 2 MINUTES)
15
F
L
LOCKOUT AC POWER FAIL (EP165, EP166)
16
10
L
LOCKOUT SHORT CIRCUIT TERMINAL 5, 6 or 7
17
11
L
LOCKOUT D-8 LIMIT OPEN
18
12
L
LOCKOUT M-D LIMIT OPEN
19
13
L
LOCKOUT FLAME FAIL - MTFI
20
14
L
LOCKOUT FALSE FLAME
21
15
L
LOCKOUT 3-P INTLK OPEN (PURGE)
22
16
L
LOCKOUT 3-P INTLK CLOSED
23
17
H
HOLD 3-P INTLK CLOSED
24
18
H
HIGH FIRE PURGE
25
19
R
PLEASE WAIT (INITIALIZING)
26
1A
L
LOCKOUT 3-P INTLK OPEN -AUTO
27
1B
L
LOCKOUT 3-P INTLK OPEN (MTFI)
28
1C
L
LOCKOUT 3-P INTLK OPEN (PTFI)
29
1D
L
LOCKOUT 13-3 FVES OPEN
30
1E
31
1F
C
CHECK FLAME SIGNAL - PTFI
32
20
C
CHECK D-8 HI LIMIT
33
21
C
CHECK M-D LOW LIMIT (CHECK)
34
22
R
FLAME SIGNAL- PTFI
35
23
C
CHECK LOW FIRE SIGNAL
36
24
R
FLAME SIGNAL - MTFI
37
25
L
LOCKOUT FLAME FAIL (AUTO)
38
26
H
HOLD 3-P INTLK OPEN - PURGE
39
27
L
LOCKOUT FUEL VALVE STATE CHANGE
E300 EXPANSION MODULE LOCKOUT MESSAGES
40
28
L
3-P AIR FLOW OPEN
41
29
L
3-P HIGH WATER
42
2A
L
3-P LOW WATER
43
2B
L
3-P HIGH GAS PRESSURE
44
2C
L
3-P LOW GAS PRESSURE
45
2D
L
3-P LOW OIL PRESSURE
46
2E
L
3-P LOW OIL TEMPERATURE
47
2F
L
3-P LOW ATOMIZING MEDIA
48
30
L
3-P HIGH STEAM PRESSURE
49
31
L
3-P HIGH TEMPERATURE
50
32
L
3-P AUX #4 OPEN
51
33
L
3-P AUX #5 OPEN
52
34
L
3-P AUX #6 OPEN
53
35
L
3-P FUEL SELECT