24
®
USER PROGRAMMED E300 MESSAGES
In addition to selecting the lockout alarm messages for the E300 Expansion Module from a menu
selection via the ED510 display, the user can also program any message (up to 40 characters in
length) for the individual terminals of the E300 using a dumb terminal (or PC with communication
software) and the appropriate interface cables. Refer to bulletin E-3001 for complete details.
PROGRAM SETUP
The sub-menu “PROGRAM SETUP” allows the user to review the various operational settings of
the programmer module (e.g. programmer type, purge timing, etc.). The MODE key is used to enter
the “PROGRAM SETUP” sub-menu, and the SCRL key is used to advance through the sub-menu.
Press
Screen Displays
Description
SCRL
AUTO
45
SCRL key advances through the historical information until
PROGRAM SETUP >
“Program Setup” is displayed. Control has released to auto
modulation, flame signal strength = 45.
MODE
AUTO
45
Programmer Type is an EP(D)160.
PROGRAMMER EP(D)160
SCRL
AUTO
45
Software Engineering code of the programmer module is code 28.
ENGR CODE NO. 28
SCRL
AUTO
45
Amplifier module is an EUV1 or an ERT1.
AMP = EUV1 OR ERT1
SCRL
AUTO
45
Purge timing (selected by the dipswitches) is 30 seconds.
PURGE TIME 0:30
SCRL
AUTO
45
Proven 3-P Open To Start is disabled (selected by dipswitches).
PROVE 3-P OPEN = N
SCRL
AUTO
45
Flame Failure Response Time (FFRT) = 4 seconds (maximum).
FLAME FAIL TIME 4s
SCRL
AUTO
45
Unit Address is 00. Refer to programmer bulletin to modify Unit
UNIT ADDRESS #00
Address.
MODE
AUTO
45
MODE key returns to run message.
FLAME SIGNAL