18
®
The control has finished purge and the firing rate motor is driving to the low fire
position (term. 10-12 made) waiting for the low fire start switch (term. M-D) to
close. It will hold this position for ten (10) minutes and then lockout if the M-D
circuit does not close, excluding the EPD167.
The running interlock circuit (3/P) has not closed within the first ten (10) seconds
of purge. The control will hold for ten (10) minutes and then lockout.
Applies to
recycle programmers only.
Flame has been sensed during the burner off time (term. L1-13 open) or during the
purge period. This message will hold for sixty (60) seconds and then lockout if
flame is still present. Flame signal strength is displayed in the upper right hand
corner.
LOCKOUT MESSAGES
Dipswitch #6 (3-P Proven Open to Start) is set in the Up position (Enabled). At the
start of the cycle, the 3-P circuit was closed, and the control has waited 60 seconds
for the 3-P circuit to open.
The control has held for more than 10 minutes waiting for the high fire switch (D-
8) to close.
Applies to EP(D)160, EP(D)161, EP165, EP166, EPD167 and
EP(D)170 programmers.
Dipswitch #6 (3-P proven open to start) is set in the Up position (Enabled). The
D-8 circuit has been closed for 30 seconds at the start of cycle.
Applies to
EP(D)160, EP(D)161, EP165, EP166, EPD167 and EP(D)170 programmers
Dipswitch #6 (3-P proven open to start) is set in the Up position (Enabled).The M-
D circuit has been closed for 30 seconds at the end of high purge or at the begin-
ning of low fire start.
Applies to EP(D)160, EP(D)161, EP165, EP166, EPD167
and EP(D)170 programmers
The running interlock circuit (3-P) has opened during the purge period or failed to
close within the first 10 seconds of purge on non-recycle programmers or has not
closed within 10 minutes on recycle programmers.
The fuel valve end switch wired between terminals 13 and 3 opened during purge
or at start up.
The control has held for more than 10 minutes waiting for the low fire switch
(M-D) to close. This does not apply to the EPD167 or EP387.
The running interlock circuit (3-P) has opened during the pilot trial for ignition
period.
Applies to non-recycle programmers only.
The running interlock circuit (3-P) has opened during the main trial for ignition
period.
Applies to non-recycle programmers only.
The running interlock circuit (3-P) has opened during the main burner on period.
Applies to non-recycle programmers only.
HOLD PURGE
0:00
M-D LIMIT OPEN
HOLD PURGE
0:10
3-P INTLK OPEN
HOLD STANDBY
25
FALSE FLAME
LOCKOUT STANDBY
3-P INTLK CLOSED
LOCKOUT PURGE
D-8 LIMIT OPEN
LOCKOUT PURGE
D-8 LIMIT CLOSED
LOCKOUT PURGE
M-D LIMIT CLOSED
LOCKOUT PURGE
3-P INTLK OPEN
LOCKOUT STANDBY
13-3 FUEL VALVE END SWITCH
LOCKOUT PURGE
M-D LIMIT OPEN
LOCKOUT PTFI
3-P INTLK OPEN
LOCKOUT MTFI
3-P INTLK OPEN
LOCKOUT AUTO
3-P INTLK OPEN