ROUGH FRAMING DIMENSIONS
A
B
C
The numbers listed are the framing dimensions recommended by FireRock, which add ½” of air space to the required clearances.
Always maintain the stated minimum clearance to combustibles for this unit.
For ease of installation, it is recommended to not install framing header until after firebox is installed.
Rough framing dimension “A” includes the 3 3/4” thick base plate. Dimension “A” should be reduced by 3 3/4” if the base plate is
eliminated to create a “flush hearth.” A raised hearth requires additional rough opening height for dimension A equal to the height
of the raised hearth detail.
FIREBOX SIZE
30”
36”
42”
48”
A
47.5”
56.25”
56.25”
64.75”
B
30”
30”
30”
30”
C
41”
47”
53”
59”
FIGURE 3
Failure to maintain stated minimum clearance to combustibles on page 12 may result in a fire or explosion, causing property
damage, personal injury, or loss of life.