Page | 5  

3

 

Design Considerations 

3.1

 

Main Power Supply Input 

The FP-08450 Fire Control Panel provide a single power supply input that is compatible with 
12 / 24vDC.  If adequate power is not supplied, the LEDs will not be  illuminated, and  the 
control panel will not operate.  The main power supply should be connected directly to a battery 
or power source, not through a distribution board. The main power must not be interrupted if 
the vessel is powered down. The FirePro Battery Lead (P/N FP-14016) may be used to connect 
power to the control panel.   
The recommended configuration i

s to use the vessel’s emergency batteries, provided that the 

vessel has an automatic changeover for its power supply. 

3.2

 

Backup Power Supply Input 

A secondary power supply is required for marine installations.  Where the vessel’s emergency 

batteries are not suitable, the control panel will need to be connected to a secondary power 
supply or the FP-08870/08871 Power Control Module will be required.  

The secondary power 

supply should be connected directly to a battery or power source, not through a distribution 
board. The secondary power supply must not be interrupted if the vessel or main power supply 
is powered down.  

Note: 

The secondary power supply 

must 

be the same voltage as the main 

power source.

 

3.3

 

Siren/Strobe Output 

A siren is required for all marine installations.  The recommended siren/strobe is the Flashni 
Xenon Sounder Beacon.  In a typical install, the maximum number of supported sirens/strobes 
that can be installed is 5.  When installed, Siren/Strobes are to be clearly visible and audible 
at all points around the risk area. 
The siren/strobe output is a monitored circuit.  The supplied end-of-line diode (1N4004) must 
be installed on the last siren/strobe in the circuit, otherwise the fire control panel will display 
a fault. 

3.4

 

Discharge Output 

The  maximum  number  of  FirePro  generators  able  to  be  discharged  by  the  FP-08450  Fire 
Control Panel is limited by the voltage of the main power supply.  That is: 

Voltage 12vDC

 

Max = 2 Units

 

Voltage 24vDC

 

Max = 4 Units

 

If  a  risk  area  requires  a  greater  number  of  FirePro  generators  to  be  discharged  than  the 
standard panel can provide, the FP-08850 Discharge Delay module can be used.  The module 
will discharge generators in multiples up to the maximum as above. 

If the number of FirePro generators connected to each output is greater than the 
maximum, the fire system will not operate. 

When multiple FirePro generators are connected to a single output, they

 must

 be connected 

using the FP-08919 Splitter Lead (see 3.9 Connecting Multiple FirePro Generators). 
If a suppression system is not used, the supplied end-of-

line resistor (3k3Ω) must be connected 

to the Discharge output using the supplied deutsch plugs. 

Содержание FP-08450

Страница 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Страница 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Страница 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Страница 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Страница 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Страница 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Страница 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Страница 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Страница 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Страница 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Страница 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Страница 12: ...Page 12 5 Wiring Diagram...

Страница 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Страница 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Страница 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Страница 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Страница 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Страница 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Страница 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Страница 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Отзывы: