background image

Page | 16  

8

  

Commissioning (Continued)

 

9.

 

While performing discharge test, ensure operation of all installed shutdown relays.  This 
should  include shutdown  of  fuel  supply,  forced  air  ventilation  and  any  other  equipment 
specified in the system design and risk assessment. 

10.

 

Individually  test  the  function  of  all  connected  detection  devices.    Testing  method  will 
depend on the specific device - check product manual if unsure. 

11.

 

Ensuring the control panel is not in an alarm/fault condition, isolate the control panel. 

12.

 

Disconnect the FirePro FP-08800 Universal Test Lamp and reconnect all installed FirePro 
aerosol generators.   

13.

 

Turn off the Isolation function. System is now operational. 

9

 

Servicing and Maintenance 

Inspection  and  servicing  of  the  installed  fire  system  should  occur  in  accordance  with  the 
relevant Australian Standards (i.e. AS1851 or AS5062).   
Any alterations to the risk area should be recorded and where necessary the risk assessment, 
design  calculation  and  installed  components  must  be  revised  to  reflect  the  new  operating 
conditions.   
A  logbook  must  be  kept,  recording  all  the  relevant  information  from  the  installation  and 
servicing.  The logbook must contain the following:

  

Content of logbook: 

Appendices of Logbook: 

General details 
Devices used 
Date of each inspection 

Outcome of each inspection

 

Schematic diagrams 
Photos of the original Installation 
Programming of the control panel  
Inspection reports

 

9.1

 

Daily Service Schedule 

A daily inspection should be performed by the operator prior to operation of the equipment.  
If anything does not appear normal, the equipment should not be operated and the fire service 
provider alerted.  The Daily Inspection should include: 
-

 

Visual inspection of the control panel and installed components.  These should be accessible 
and free from debris, rust, or electrical faults. 

-

 

Visual  inspection  of  the  control  panel  to  ensure  normal  functioning.    When  functioning 

normally the only indicator illuminated should be the “Power” indica

tor (green). 

-

 

Visual inspection of anti-tamper seals and travel pins, to ensure they are in place. 

9.2

 

Semi-annual / Annual Service Schedule 

Semi-annual  and  Annual  servicing  and  maintenance 

are  to  be  undertaken  only  by 

accredited service technicians.

  Any misuse of the FIP may result in an accidental discharge 

of the suppression system and is not covered by warranty.

 

Servicing should include a visual inspection of all the installed components to ensure they are 
in good condition, and that the relevant stream lengths and thermal clearances are observed 
as per the original design calculation and risk assessment.  
Operation of the fire system should be tested as outlined in 8. Commissioning. 

Содержание FP-08450

Страница 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Страница 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Страница 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Страница 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Страница 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Страница 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Страница 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Страница 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Страница 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Страница 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Страница 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Страница 12: ...Page 12 5 Wiring Diagram...

Страница 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Страница 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Страница 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Страница 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Страница 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Страница 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Страница 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Страница 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Отзывы: