Siren/Strobe Circuit: 

Mount the siren/strobe (P/N FP-08940) in a location where it is 

visible and audible in all points with the risk area and connect 

to the “Siren” output on the 

module (marked orange).  If more than one siren/strobe is being installed, they are to be 
connected using the secondary positive/negative terminals in the sounder.

 

The  supplied  end-of-line  diode  should  be  installed  in  the  secondary  positive/negative 
terminals of the last siren/strobe in the circuit.  The diode is polarised, so the positive lead 
of the diode (marked with a grey band) should be terminated in the positive terminal of 
the siren/strobe, otherwise a fault will occur on the fire control panel.

  

 

4.

 

Circuit  1  Alarm  Circuit: 

This  circuit  can  be  programmed  for

  ALARM  ONLY

  (operate 

siren/strobe) or 

AUTOMATIC DISCHARGE

 (discharges suppression system and operates 

siren/strobe).  If detection is not used, the supplied end-of-line plugs (marked green) must 
be connected to the Circuit 1 Alarm output.

 

-

 

Manual Call Point:  

Manual Call Points (P/N FP-14053) can be connected together in 

quantities up to 30.  If a manual call point is being used for remote activation, it 

must

 

be installed on Circuit 1 Alarm.  The supplied end-of-line plugs (marked green) must be 
connected to the last manual call point in the circuit.

 

 

-

 

Linear Heat Detection:  

Linear Heat Detection can be installed in lengths up to 100m.

 

Any terminations of cable must be enclosed using sealed, metal enclosures from the 
LHD Install Kit (P/N FP-09511).  P-Clips must be installed at intervals of 50cm maximum 
to support the cable.  The supplied End-of-line junction box must be installed on the 
end of the cable. 

 

 

 

Содержание FP-08450

Страница 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Страница 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Страница 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Страница 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Страница 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Страница 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Страница 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Страница 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Страница 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Страница 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Страница 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Страница 12: ...Page 12 5 Wiring Diagram...

Страница 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Страница 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Страница 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Страница 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Страница 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Страница 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Страница 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Страница 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Отзывы: