Mantel Requirements
¥
The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it
is considered a mantel and must meet the mantel requirements listed in this manual.
Combustible Mantels
Combustible Mantel
30" Arch face
28-1/2" Rectangular face
24Ó Min. Arch Faces
22Ó Min. Rect. Faces
Max.
Mantel
Depth is
8Ó
Non-Combustible Mantel
Non-Combustible mantels must maintain a 12"
clearance to the top of the face and be located
below the header -or- maintain a 24" clearance.
Header
46-1/8"
Non-Combustible
Mantels
Min. 12"
30" Arch face
28-1/2" Rectangular face
Max.
Mantel
Depth is
8Ó