Finalizing the Installation
(for qualified installers only)
© Travis Industries
4161018
100-01436
Facing Requirements
The fireplace requires non-combustible facing (typically 1/2" thick concrete-board) from the base of
the fireplace to the header (min. 81”). The non-combustible facing must extend to the framing
members on both sides of the fireplace. Do not use drywall or other combustible in this area (see
illustration below).
The non-combustible facing may be attached to the front of the fireplace with screws. Do not
penetrate the fireplace more than 3/4”.
Facing over 1” thick (brick, thick marble) may be used around the perimeter of the faceplate.
Non-Combustible Facing
Minimum 81"
Minimum 42"
Drywall
Combustible Framing
(min. 81" from base of fireplace)
Tile (or other non-
combustible facing)
Non-Combustible Framing
(included with fireplace)