FPB Pro Spur Burners Fire Pits with AWS System

REV. A            Page 16

•  Insufficient Power 

- If the glow plug is not getting enough power, it will not get ignite the gas.

•  Thin Wire

 -  The recommended minimum wire gauge is 12AWG .  If wire is less than 12-gauge there may not be 

enough power to get the igniter hot enough.

•  No Gas

 - Was the gas line purged of air?  If gas line was not bled it may take a while before the gas gets to the fire 

feature.

•  Manual Shut Off Valve

 - Is the manual shut-off or key valve open?

•  Debris 

- Debris can get trapped inside the screen of the gas valve.  Excessive amounts of pipe dope or Teflon tape 

can restrict gas flow.

•  Debris in Pilot Burner

 - New gas lines, until bled, have air and will have some debris.  Ensure gas it turned OFF and 

electrical is unplugged.  Remove the two brass fitting from the gas valve, then use “canned air” to blow through the 

pilot outlets.

•  Wrong Pilot Orifice 

- If the wrong pilot orifice is installed into the primary pilot it will not light.

•  Oxygen Starvation

 - To ignite gas we need oxygen, fuel and a heat source.  If the pilot assembly is buried under-

neath the glass media or lava rock it will not allow the pilot to light.

•  Weak Igniter

 - In some cases, from the manufacturer’s glow plug will have slight difference in assembly which can 

cause some igniter’s burn hotter than others.  These are tested before they are sent to customers but sometimes a 

weak one can get out. If this occurs, the symptom will always be the same - inconsistent or no ignition at all. In this 

case, replace the pilot burner.

•  Valve Box Installed Backwards - 

Check the label on the gas valve box and ensure the burner is connected to the    

OUTLET side of the gas valve box.

•  Thermopile Pins Not Secure

 - Check the pins in the pilot burner connector, remove it from the gas valve and check 

for loose pins.  If loose, push inward until tight and try again.  If this happens, the glow plug will stay ON for up to 30 

seconds before turning OFF.  It normally shuts off in about 5 seconds.

•  Defective Thermopile

 - Thermopile’s rarely go bad however if a product is used consistently for extended periods 

of time a thermopile can get too hot (like a blow torch) and eventually cause it to swell. Simply loosen the thermopile 

from the pilot assembly and slide it out.  If it will not slide out because is it too tight, then it will need to be replaced.

•  Debris 

- Debris can get trapped inside the screen of the gas valve.  Over time rust and other debris can restrict the 

gas flow on the Outlet screen of the valve that can partially or sometimes even stop the flow.  Inspect the screen, 

remove it and clean it then replace it. 

•  Defective Controller or Main Gas Valve

 - If you have inspected the thermopile connections and no debris is on the   

controller or gas valve; checked the power, then the gas valve or controller may be defective and will need replaced.

3. Glow Plug Glows, But Does Not Ignite the Gas

4. Pilot Lights, But No Flame to the Main Burner

5. Fire Features Lights... Turns OFF Within A Few Seconds... 

and Restarts Again (Keeps repeating this sequence)

•  Gas Volume Insufficient - 

When initially turning ON the fire feature pilot is lit and there is enough gas for the pilot to 

light, however once main gas valve is turned ON, the flow of gas to pilot drops not providing enough gas to keep the 

thermopile hot enough therefore the pilot will drop out and relight. This is usually caused by insufficient Gas Volume 

and can be caused by installing gas pipe too small to deliver proper amount of gas or by installing a Manual Gas 

Shutoff (Ball valve or Key Valve) with a capacity that is too small to allow enough gas to pass through to the feature.

•  Main Burner Orifice Not Installed

 - Ensure the correct orifice is being used.  If using LP gas it should have vent 

holes, Natural gas does not.  See Fig. 4, page 8.  The orifice/air mixer restricts the amount of gas flowing to the Main 

Burner. This restriction ensures that not ALL the gas will flow to the Main Burner, so there is still enough gas left for 

Pilot Burner.

•  Oxygen Starvation

 - to ignite gas we need oxygen, fuel and a heat source.  If the pilot assembly is buried underneath 

the glass media or lava rock it will not allow the pilot to light.

•  Defective Thermopile

 -  See Symptom 4 above for Defective Thermopile.

•  Defective Controller

 – If your plumbing is supplying enough gas, the Main Burner orifice is installed, the Pilot Burner 

is getting plenty of air and the Thermopile is not defective the only thing left is a Defective Controller inside the valve 

box. If you have a Defective Controller the only way to fix it is to replace it.

TROUBLESHOOTING

Содержание FPB-19RPSBR14AWS-N

Страница 1: ...rovide proper ventilation will void the warranty Natural Gas Models Propane Gas Models Description FPB 19RPSBR14AWS N FPB 19RPSBR14AWS P 19 Round Pan with 14 Pro Brass Burner FPB 25RPSBR21AWS N FPB 25...

Страница 2: ...ff gas to the appliance 2 Extinguish any open flame 3 If odor continues keep away from the appliance and immediately call your gas supplier or fire department DANGER WARNING Do not store or use gasoli...

Страница 3: ...lame from distance to ensure that all popping has ceased before fully enjoying the fire CAUTION TABLE OF CONTENTS Specifications 4 Carton Contents Single Fire Feature 5 Preparing a Non Combustible Str...

Страница 4: ...As a result your Btu s may vary slightly from Table 2 specifications Table 2 Burner specifications Natural Gas Models Propane Gas Models A Depth B Min Max Opening C Inside Pan Dimension D Ground Level...

Страница 5: ...on of the stainless steel flex gas line not supplied with the fire feature see Fig 5 page 9 5 Do not place an LP tank inside any fire pit enclosure Locate all Liquid Propane LP tanks outside the enclo...

Страница 6: ...es required for the amount of BTU s for a new gas line installations If you are using an existing gas line you must take into consideration the existing gas line capacities to ensure you will have pro...

Страница 7: ...nut connec tions and connectors to prevent moisture issues from the outdoor environment The AWS system is polarity sensitive There is a red sleeve attached to the positive side of the adapter When wir...

Страница 8: ...sure the flame is a safe and reasonable height to not pose a risk to people or property Note The Firegear Pro Series brass burners DO NOT USE a primary main burner orifice like a standard stainless st...

Страница 9: ...lled inside the enclosure due to the wire length limitations The power cord is 3 feet long the 30VDC leads to the valve are 3 feet long See Fig 5 Fig 7 Example of a single fire feature install with po...

Страница 10: ...in detail enables the ability to remove the pan disc to service valve system Flex Frame Optional ON OFF Controls Note Actual power supply must be 10 feet or more from the pool or spa DETAIL Pool Contr...

Страница 11: ...S IMPORTANT DO NOT PLACE ROCK OVER TOP OR UNDER THE PILOT SCREEN COVER The screen must be free of any debris to ensure proper lighting of burner and good flame sense See Fig 13 Cover the burner comple...

Страница 12: ...r LP gas line WARNING 1 This appliance is hot when operated and can cause severe burns if contacted 2 Do not burn any solid fuels in this appliance READ ALL LIGHTING INSTRUCTIONS BEFORE ATTEMPTING TO...

Страница 13: ...REV A Page 13 FPB Pro Spur Burners Fire Pits with AWS System AWS REPLACEMENT PARTS GOE 30DCV OUT 1 4 3 2 5 6 7 8 9 10 Items are not to scale...

Страница 14: ...rner Cage hood 1 FG PBC 8 Thermopile for primary pilot assembly 1 FG TP 9 Hot Surface Ignition for pilot burner assembly item 2 1 FG HSI 10 Heat Shield 1 FG HEATSHIELD 11 Rocker Switch installs into 7...

Страница 15: ...r If for some reason someone connected 120VAC power directly to the gas valve the controller inside the valve box will be damaged It this happens a burned electrical smell might be present Connector N...

Страница 16: ...osen the thermopile from the pilot assembly and slide it out If it will not slide out because is it too tight then it will need to be replaced Debris Debris can get trapped inside the screen of the ga...

Страница 17: ...effect Remove some of the fire glass media from the burner to see if this fixes the problem Gas Leak Natural Gas is lighter than air therefore when released into the atmosphere it rises If you have a...

Страница 18: ...when using paver blocks or other non combustible enclosures Glass Windshields See catalog for a windshield to fit your application Shut Off Valves Model 01 387 OD Flare x FIP Model 01 487 OD Flare x F...

Страница 19: ...VE 5 YEAR WARRANTY REFRACTORY GAS LOG SETS FIVE 5 YEAR WARRANTY READY TO FINISH ANF FIRE PIT ENCLOSURES FIVE 5 YEAR WARRANTY SKYTECH MANUACFTURED OPTIONAL CONTROLS OUTDOOR FIREPLACE KALEA BAY LIFETIME...

Страница 20: ...FIREPLACE KALEA BAY LIFETIME WARRANTY CONSTRUCTION AND MANUFACTURER DEFECTS LIFETIME WARRANTY STAINLESS STEEL COMPONENTS TWO 2 YEAR WARRANTY GAS VALVE PILOT ASSEMBLY POWER SUPPLY CONTROLS TWO 2 YEAR...

Страница 21: ...to repair the defect on warranty parts to and from the factory will be the responsibility of the owner We will not be responsible for labor charges and or damage incurred in installation repair and r...

Страница 22: ...company to assume for it any other obligation or liability in connection with the sale installation use removal return or replacement of its equipment and or such representation are binding Firegear O...

Страница 23: ...________ 2 Serial Number ___________________________ 3 How long is the gas line run Nat Gas ____ LP Gas ____ 4 What size is gas line _____ 5 Inlet Gas Pressure _____WC Manifold Gas Pressure _____ WC 6...

Отзывы: