10
30
Burner
Smoke
Bacharach
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
CO
2
11.5%
11.5%
11.5%
11.5%
11.5%
11.5%
11.5%
11.5%
Avg.
Fg. ˚C
70
75
70
80
85
80
90
95
Air
Box
1
1
1
1
1
1
1
1
Comb
Head
-
-
-
-
-
-
-
-
Pump
Pressure
8.5 bar
8 bar
9 bar
9 bar
9 bar
9 bar
9 bar
8.2 bar
Blast
Tube
LD2X
LD2X
T3
T3
T3
T3
T3
T3
Air
Shutter
1.5
2.8
1.8
2.5
4.0
4.0
5.0
6.5
Nozzle
Size - Angle - Type
0.5
80˚
ES
0.6
80˚
ES
0.6
80˚
ES
0.65 80˚
ES
0.75 80˚
ES
0.75 80˚
ES
0.85 80˚
ES
1.00 80˚
ES
The shaded line represents factory settings. These settings override those in the burner manual.
RDB 2.2
Burne
r
15-20
20-26
26-35
Mode
l
Output
kW BTU
18 59k
20 68k
20 68k
23 79k
26 89k
26 89k
31 104k
35 120k
Restrictor
Disc
C
C
-
-
-
-
-
-
Deflector
Plate
A11
A11
STD
STD
STD
STD
STD
STD
The above performance figures are based on ideal laboratory test conditions. The air shutter settings above may need to be revised to take into consideration the
difference in resistances between conventional and balanced flue installations, air temperature and nozzle tolerance. Use flue gas analyzer to achieve optimum results.
Danfoss eS nozzles are a Kerosene nozzle and have a tolerance of +- 5%. Danfoss S + H nozzles are a Diesel nozzle and have a tolerance of +- 15% when used with Kerosene.
Kerosene settIngs for fIreBIrd BoIler range usIng rdB 2.2 Burners
variations in nozzle throughput, flue type & draught, oil viscosity etc. may give results differing from
the below laboratory performance figures. these settings were carried out using a conventional flue.
The burner nozzle, pump pressure and air setting may have to be changed from the factory setting to suit site conditions.
settIng tHe Burner
1. establish the type of fuel in the oil tank.
2. Check that the nozzle type, pump pressure and air settings are as per the manual for the output required.
3. Set the thermostat to the minimum temperature and let the boiler run until it cuts out at 60˚C.
4. The boiler must be at 60˚C or higher before any adjustments or analysing is carried out.
By doing this, you are also ensuring the thermostat is working.
5. Increase the thermostat setting to refire the burner.
6. Wait for the CO
2
to stabilise.
7. adjust the air and pump pressure to achieve a stable CO
2
in the region of 11.5%
(refer to graph under Commissioning & Burner Settings).
8. The fuel option on the flue gas analyser should be set to a light oil.
for burner technical details which are not covered in this manual, refer to the burner manufacturer’s manual