background image

5

16

CommIssIonIng

flue check: 

u

  The flue must be fitted correctly, with a fall back to the  

boiler. Note: internal fall of 2.5˚ within the flue.

u

  For concentric balanced flue:

  -  the cone supplied should be inserted in to the end     

of the flue;

  -  the wall plate should be fitted with an opening
    for air under the flue;
  -  check that the flue guard is fitted.  

u

  When installing a Silverpac or a Slimline Silverpac, the 

90˚ bend should be fitted pointing up.

Boiler set-up:

u

  For burner set-up, see page 30.

u

  Set the air to what is required for the nozzle size +. 5 on 

the dial - example: the factory setting for a Firebird 26kW 
has a Danfoss .65 80° eS nozzle with a pump pressure of 
9 bar and air at 2.5. The final air setting to suit the boiler 
set up will be determined by using a flue gas analyser.

u

  Turn on the oil supply and switch on power to the       

boiler.

u

  Check all connections for possible leaks.

u

  Check  thermostat  operation  and  set  desired                           

temperature on completion.

u

  Use a smoke gun to check clean combustion.

flue gas analysis and fine tuning of burner:

u

  ensure flue gas is over 50˚C when setting CO

2.

u

  allow the boiler to run for a period of time before fine 

tuning to the Firebird settings.

u

  Fine tuning of the burner should take place once the 

recommended oil pressure value has been obtained. 
Burner air should then be adjusted to achieve the 
desired CO

2

 setting.

u

  Print off a copy of the flue analysis and attach to the 

boiler passport.

u

  Make  sure  the  flue  gas  analysis  plug  is  replaced            

correctly into the flue when finished the flue analysis.

1% rise in CO

2

as the ambient 
temperature rises 
by 20°.

In the cold of winter 
aim for lower CO

2

%.

In warmer times of the 
year set the CO

2

 higher.

 

0

5

10

15

20

25

30

35

40

12

12.5

13

11

11.5

Outside air temperature (˚C)

CO

2

CommIssIonIng

u

  It is the responsibility of the installer to ensure that 

the boiler is properly commissioned when first used.

u

  the boiler should be commissioned by an ofteC 

registered, or competent, qualified engineer, 

 

 

familiar with firebird products.

u

  the installation certificate and the commissioning 

certificate within the boiler passport should be 
completed and posted to firebird within 28 days 
of installation (this can also be done online on the 
firebird website). a copy should be retained by the 
commissioning engineer.

u

  the system should be checked thoroughly.

CHeCKlIst for InstallIng and

CommIssIonIng a fIreBIrd BoIler

Pre-installation check:

Is  the  following  documentation  included  with  the       
boiler, Installation Manual, Boiler Passport, Burner Book?

u

  Is the base on which the boiler is to be installed solid?

u

  allow sufficient room for future servicing of the boiler.

Where does the flue terminate:

u

  Make sure there is no window, door or fence within 1 

metre of the flue-terminal.

u

  If the flue terminates in a corner or into an allyway,         

re-circulation of the combustion gases in the air intake 
could occur. a plume dispersal may be required or 
an alternative flue arrangement might be available. 
Contact the Firebird technical department for advise.

u

  The  appropriate  class  1  flue  must  be  used  with  a           

conventional flue installation. Contact Firebird if unsure.

Power supply:

u

  Is a timed, permanent, power supply available, via a 

fused spur with a 230V 50Hz mains electrical supply and 
a 5a fuse?

oil supply:

u

  The burner is set for 28 Second Class C fuel.

u

  a 15 micron oil filter should be placed in line with an 

isolating valve prior to entry to the burner.

u

  There must be a remote sensing fire valve.

u

  Verify that the oil tank has been installed correctly as 

per building standards.

Boiler check:

u

 Baffles should be checked as they may have been 

disturbed during transport.

u

 Check that the condensate trap is fitted securely, 

primed with water and piped out into a suitable drain. 
It is easier to check the trap when the boiler door is 
removed.

u

 The boiler door should be refitted, complete with 

graphite seal and then tightened.

Содержание silver Boilerhouse 15-20kW

Страница 1: ...g Boilers Technical Manual HEATING SOLUTIONS This manual must remain with the householder once installation is complete Working towards a greener planet Silverpac Slimline Silverpac Silver Boilerhouse...

Страница 2: ......

Страница 3: ...rpac 22 8 2 Slimline Silverpac 23 8 3 Silver Boilerhouse 24 8 4 Silver Utility 25 9 Wiring 9 1 Silverpac 26 9 2 Slimline Silverpac 27 9 3 Silver Boilerhouse 28 9 4 Silver Utility 29 10 Burner 30 11 Te...

Страница 4: ...let First Aid medical attention should be sought following eye contact or prolonged reddening of the skin The small quantities of adhesives and sealants used in the product are cured They present no k...

Страница 5: ...status lights not included in Silver Boilerhouse and Silverpac models Set at Max 80 C Set at Mid 70 C Set at Min 60 C Burner Lockout The boiler is factory fitted with a burner control box lockout safe...

Страница 6: ...12 A1 2014 BS EN 12831 2003 and the statutory requirements of the Building Regulations To ensure the highest standards of installation safety it is important that the boiler be installed in compliance...

Страница 7: ...g manuals and BS 7074 Part 1 EN 12828 2003 etc Please note following important points before commencing installation Installation Commissioning Boilers must be installed commissioned and serviced by a...

Страница 8: ...r the cleaning door This should be checked at regular intervals and cleaned during annual service The condensate line should be plastic and have a minimum diameter of 22mm dia have a fall from the boi...

Страница 9: ...re connecting the condensate pump Condensate PUMP kit is available as an optional extra Boiler Sealed Condensate Drain Condensate Drain Trap Lime Stone Chippings Free Draining Soil Soak Away 500mm Fig...

Страница 10: ...Cone Float Screw cap Seal Seal 1 Push screw cap into connector and screw onto socket 2 Place cone into frame and float into cone 3 Screw frame with cone and float into connector 5 Final assembly 4 Pus...

Страница 11: ...Q Q R Pressure Jet Location Appliance Burner Type Condensing UK ROI NI A Directly below an opening airbrick opening window etc 1000mm 600mm B Horizontally to an opening airbrick opening window etc 100...

Страница 12: ...to BS EN 303 1 5 Terminating positions must be at least 1 8m distant from an oil storage tank unless a wall with at least 30 minutes fire resistance and extending 300mm higher and wider than the oil s...

Страница 13: ...ired to ventilate and to avoid overheating in the boiler area OPEN FLUE BOILER IN ROOM BOILER COMPARTMENT VENTILATED FROM OUTSIDE BOILER COMPARTMENT VENTILATED FROM ADJOINING ROOM 55mm2 kW 55mm2 kW 55...

Страница 14: ...Balanced flue TOP mark Snorkel 1 Push the flap valve into the balanced flue air intake 2 Ensure that the flap valve is in the correct position 3 Push the snorkel hose over the flap valve and air inta...

Страница 15: ...LVERPAC SLIMLINE SILVERPAC FLUE Put the 90 flue terminal with the cone on the boiler Fix the guard plate to the boiler and then the guard to the boiler Heatpac boiler after installation Fig 1 Fig 2 Fi...

Страница 16: ...ate System 35 flexible liner suitable for condensing applications System 35 adaptor 500mm Adjustable length Boiler adaptor Condensing boiler Condensing boiler NOTE All brick chimney constructions must...

Страница 17: ...oil tight Soldered joints are not permissible Before connecting to the boiler always flush the complete oil supply line and ensure that oil supply is completely clean and free of any dirt or foreign m...

Страница 18: ...erly commissioned when first used u The boiler should be commissioned by an OFTEC registered or competent qualified engineer familiar with Firebird products u The installation certificate and the comm...

Страница 19: ...the chamber 3 Clean the inside of the boiler with a vacuum cleaner 4 Refit all the baffles and the condensate trap securely 5 System pressure should not exceed 2 bar at full operating temperature The...

Страница 20: ...S 7074 Part 1 BS 5449 OFTEC standards and all other relevant legislation Preset Pressure Relief Valve 2 bar Water Side Resistance 15 20kW 20 26kW 26 35kW Flow Rate To Give A Nominal Output At 10K Diff...

Страница 21: ...d all other relevant legislation Preset Pressure Relief Valve 2 bar Water Side Resistance Flow Rate To Give A Nominal Output At 10K Differential Flow Rate Measured 2135 kg h Waterside Resistance 0 18...

Страница 22: ...ive A Nominal Output At 10K Differential Flow Rate Measured 1642 kg h 2135 kg h 2874 kg h Waterside Resistance 0 18 mbar 0 18 mbar 0 18 mbar Flow Rate To Give A Nominal Output At 20K Differential Flow...

Страница 23: ...W Flow Rate To Give A Nominal Output At 10K Differential Flow Rate Measured 1642 kg h 2135 kg h 2874 kg h Waterside Resistance 0 18 mbar 0 18 mbar 0 18 mbar Flow Rate To Give A Nominal Output At 20K D...

Страница 24: ...1 Condensate hose 111537 111537 111537 9 1 Drain cock 111329 111329 111329 10 1 Heat deflector 210904 210904 210904 11 1 Flap valve adapter 114262 114262 114262 12 1 Flap valve 114192 114192 114192 13...

Страница 25: ...ket 111317 7 1 Condensate trap 112184 8 1 Condensate hose 111537 9 1 Drain cock 111329 10 1 Heat deflector 210904 11 1 Flap valve adapter 114262 12 1 Flap valve 114192 13 1 Flue kit 411482 14 1 Contro...

Страница 26: ...Flue gasket 112104 112104 112104 6 1 Stat pocket 111317 111317 111317 7 1 Condensate trap 112184 112184 112184 8 1 Condensate hose 111537 111537 111537 9 1 Drain cock 111329 111329 111329 10 1 Heat de...

Страница 27: ...317 111317 7 1 Condensate trap 112184 112184 112184 8 1 Condensate hose 111537 111537 111537 9 1 Drain cock 111329 111329 111329 10 1 Heat deflector 210904 210904 210904 11 1 Air hose 111902 111902 11...

Страница 28: ...hermostat Reset pin inside Screw off cover Temperture control dial Max 80 C Min 60 C IMIT dual thermostat Pump live Earth Neutral Permanent live Timed Switch live Neutral Earth Pump over run thermosta...

Страница 29: ...e provided for with terminal connections in the control panel Use heat resistant cable Protect supply with 5A fuse Power to burner High temperture limit thermostat Reset pin inside Screw off cover Tem...

Страница 30: ...ids and covers are properly replaced and secured correctly 4 A permanent power supply not timed should be available at boiler location This can be used for a frost thermostat and or an over heat therm...

Страница 31: ...h temperture limit thermostat Reset pin inside Screw off cover Temperture control dial Max 80 C Min 60 C IMIT dual thermostat L1 switch live Pump over run thermostat 87 C L2 remote lockout lamp Please...

Страница 32: ...Danfoss S H nozzles are a Diesel nozzle and have a tolerance of 15 when used with Kerosene KEROSENE SETTINGS FOR FIREBIRD BOILER RANGE USING RDB 2 2 BURNERS Variations in nozzle throughput flue type...

Страница 33: ...accordance with a instruction technical manuals b all relevant standards and codes of practice 4 An OFTEC registered or competent qualified engineer using the correct installation and test equipment...

Страница 34: ...ergy Consumption Sound Power Level kW GJ dB SILVERPAC 15 20kW A 20 92 50 N A 20 26kW A 26 92 72 N A 26 35kW A 35 92 95 N A SLIMLINE SILVERPAC 20 26kW A 26 92 72 N A SILVER BOILERHOUSE 15 20kW A 20 92...

Страница 35: ......

Страница 36: ...contact Firebird Heating Solutions Ltd dar s Industrial Estate Baile Mhic re Co Cork P12 HK51 Ireland t 353 0 26 45253 f 353 0 26 45309 e info firebird ie web www firebird ie Firebird Heating Solution...

Отзывы: