Model FS17X
™
Fire and Flame Detector
INSTALLATION GUIDE and OPERATING MANUAL
Fire Sentry Corporation
Document No. 6178-007 - Rev. F
© Copyright 2012
All Rights Reserved
Page 5
2.2
Detector Connections
The FS17X-G and FS17X-S Detectors have eight (8) connections available with the Standard Cable. These
connections are subject to the Output Configuration of the Detector at the time the order is placed. These
Output Configurations are:
#1
RS-485 FireBus
II
II
II
II
(
FS17X-G & FS17X-S
)
#2
Quick Response Fireball Relay (
FS17X-G & FS17X-S
)
#3
Fire Verification Relay (
FS17X-G & FS17X-S
)
#4
Current sinking 4-20mA (
FS17X-G & FS17X-S
)
Color Code for
Standard Cable
Output
Configuration #1
Output
Configuration #2
Output
Configuration #3
Output
Configuration #4
Red
+24 Vdc
+24 Vdc
+24 Vdc
+24 Vdc
Black
DC Return
DC Return
DC Return
DC Return
Green
FireBus
II
Data A RS-485
Quick Response
Fireball Relay
N
.
O
. (
N
ormally
O
pen)
Fire Verification Relay
N
.
O
. (
N
ormally
O
pen)
Current Sinking
4-20mA (+)
White
FireBus
II
Data B RS-485
Quick Response
Fireball Relay
COM
(
COM
mon)
Fire Verification Relay
COM
(
COM
mon)
Current Sinking
4-20mA (-)
Orange
Fire ALARM Relay
N
.
O
. (
N
ormally
O
pen)
Fire ALARM Relay
N
.
O
. (
N
ormally
O
pen)
Fire ALARM Relay
N
.
O
. (
N
ormally
O
pen)
Fire ALARM Relay
N
.
O
. (
N
ormally
O
pen)
Blue
Fire ALARM Relay
COM
(
COM
mon)
Fire ALARM Relay
COM
(
COM
mon)
Fire ALARM Relay
COM
(
COM
mon)
Fire ALARM Relay
COM
(
COM
mon)
Yellow
Fault Relay
N
.
C
.
(
N
ormally
Closed
)
Fault Relay
N
.
C
.
(
N
ormally
Closed
)
Fault Relay
N
.
C
.
(
N
ormally
Closed
)
Fault Relay
N
.
C
.
(
N
ormally
Closed
)
Brown
Fault Relay
COM
(
COM
mon)
Fault Relay
COM
(
COM
mon)
Fault Relay
COM
(
COM
mon)
Fault Relay
COM
(
COM
mon)
The following Relays have a Normally Closed (N.C.) option: Fire ALARM, Quick Response Fireball, and Fire
Verification.
1. Make sure that the external 24 Vdc electrical power is turned
U
OFF
U
before connecting the Detector.
2. Avoid wire splices. However, if wire splices are required, all splices should be soldered and properly
insulated. The use of good wiring practices will simplify installation, improve reliability and facilitate
maintenance.
CAUTION:
Follow static protection procedures while handling the connectors and the
wiring of the FS17X Detector. Use a wrist strap connected to earth ground.