Model FS17X
™
Fire and Flame Detector
INSTALLATION GUIDE and OPERATING MANUAL
Fire Sentry Corporation
Document No. 6178-007 - Rev. F
© Copyright 2012
All Rights Reserved
Page 1
SECTION 1: INTRODUCTION
1.1
Product Overview
The Model FS17X
™
Electro-Optical Multi-Spectral Detector
senses the WideBand Infrared™ (IR) radiant energy of
blackbody particulate and molecular emissions generated by
both hydrocarbon and non-hydrocarbon flames and fires.
Additionally, the Detector’s sensor array senses Visible Band
(VIS) and NearBand IR to further discriminate against false fire
sources. The FS17X WideBand Multi-Spectral sensor array
spans 0.4 to 3.0 microns and features a wide 120° field of
view.
The Model FS17X Multi-Spectral Fire and Flame Detector
is Factory Mutual approved for use in Class
I,
Division
2
(
Zone
2) Hazardous Locations (
see Figure 1-1)
.
The FS17X Detector available in a polypropylene housing, is
rated IP67, dust tight, leak-proof and water tight to 1 meter.
Figure 1-1
FS17X Detector
FS17X Connections
The Model FS17X uses an eight (8) conductor Standard Cable or an optional eight (8) conductor Cable with a
Phoenix Connector for inputs and outputs. Every
FS17X
has the following six (6) connections:
1.
+24 Vdc & DC Return
2.
Fault
N
.
C
. (
N
ormally
C
losed) &
COM
(
COM
mon)
3.
ALARM
N
.
O
. (
N
ormally
O
pen)¹ &
COM
(
COM
mon)
There are 2 options for the
FS17X-S
Detector:
S1. Quick Response - Fireball
N
.
O
. (
N
ormally
O
pen)¹ &
COM
(
COM
mon) or
S2. RS-485 Data A & Data B
There are 4 options for the
FS17X-G
Detector:
G1. RS-485 Data A & Data B
or
G2. Quick Response - Fireball
N
.
O
. (
N
ormally
O
pen)¹ &
COM
(
COM
mon)
or
G3. Fire Verification
N
.
O
. (
N
ormally
O
pen)¹ &
COM
(
COM
mon)
or
G2. Current sinking 4-20mA (+) & (-)
¹
Optional N.C. (Normally Closed) Relay Contacts are available.
FS17X Configurations
The Model FSX has several factory configurations to choose from:
Auxiliary:
Alert (-R)
or
Fireball Quick Response (-S or -G)
or
Fire Verification (-G)
Fire Verification Time
: 5
or
10 second
Relay Outputs
: Latching
or
Non-latching
Detection Sensitivity
: High
or
Low
Digital Communication Address
: 0 to 32