2.3 

Installation Practices 

For  installations  in  a  Hazardous  Classified  Area,  consult  the  National  Electric  Code  Handbook,  Articles  500 
through  517  for  the  proper  installation  practices.    For  locations  outside  of  the  United  States,  observe  local 
and/or regional regulations. 

 

BEFORE APPLYING 24 Vdc ELECTRICAL POWER TO THE DETECTOR, MAKE SURE

U

1.  Wire connections are correct (Section 2.2).  Each wire must be stripped properly to the correct length, 

loose wire strands must be removed and each wire must be securely and firmly screwed clockwise in 
the connector. 

2.  If  using  the  Teflon  Sleeve,  ensure  a  proper  sleeve  seal  at  the  bulkhead,  (appropriate  for  the  area 

classification),  has  been  installed  and 

U

all  measures  to  prevent  moisture  from  entering  the 

Detector housing have been taken

U

.

 

3.  The  FS17X  Detector  is  securely  mounted  and  has  an  unobstructed  view  of  the  area  of  coverage 

(Section 2.1). 

4.  The FS17X Detector window is unobstructed and clean. 

 
The FS17X Detector is now ready for Power-Up.  

On Power-Up, the Fault Relay will change state and the 

three  front  red,  blue,  and  yellow  LED’s  will  flash  in  a  clockwise  circular  motion  signifying  the 
microprocessors are successfully checking out the sensors and electronics in the Detector Module

.

  

 

2.4 

Start-Up and Commissioning 

ATTENTION

FSX Power-Up

 – After the application of 24 Vdc electrical power or after resetting the FS17X 

Detector,  a  Power-On  Self-Test  (POST)  will  be  performed  automatically.    During  this  time 
(approximately 10 seconds) the detector will sequence in a clockwise circular motion through the its 
LED’s several times.  Wait a mimimum of thirty (30) seconds after the POST is completed to allow 
the Detector’s sensors to normalize to the spectral background conditions.  Count four (4) Blue LED 
flashes  to  be  sure  the  minmum  amount  of  time  has  passed  before  testing  the  Detector’s  response 
with a test lamp (TL-2055X or TL-1055X) or a test fire. 

 

FSX  Detector  Testing

  -  As  with  any  intelligent  flame  and  fire  Detector,  please  wait  a  minimum  of 

thirty  (30)  seconds  between  tests  (i.e.,  FSX  test  lamp,  butane  lighter,  or  test  fires)  to  allow  the 
Detector’s sensors to normalize to the spectral background conditions.   
 

 
During Start-Up and Commissioning, 

DISABLE

 all outputs from the Detector to any control panels or control 

devices.  After the Detector(s) is powered, as with all flame and fire Detectors, conduct an external Detector 
test “end to end”.  Using our external FSX hand-held test lamp ensures that the FS17X Detector has a clear 
unobstructed view of the threat area and the Detector is aimed properly at the fire threat area. 
 

 
 
 
 
 
 
 
 
 

Содержание FS17X

Страница 1: ...t 2012 All Rights Reserved Fire Sentry Corporation 23311 La Palma Avenue Yorba Linda California 92887 Telephone 714 694 2700 Fax 714 694 2701 www firesentry com FS17X WideBand IRTM Multi Spectral Infr...

Страница 2: ...ns such as FS2 FS2X FS2X FS3 FS3X FS3X FS4 FS4X FS4X FS5 FS5X FS5X FS6 FS6X FS6X FS7 FS7X FS7X FS8 FS8X FS8X FS9 FS9X FS9X FS10X FS10X FS11 FS11X FS11X FS12 FS12X FS12X FS14 FS14X FS14X FS15 FS15X FS1...

Страница 3: ...pecifications 2 1 2 5 Area Classification 2 1 3 Features Benefits 3 1 4 Applications 3 SECTION 2 INSTALLATION 4 2 1 Mounting Instructions 4 2 2 Detector Connections 5 2 3 Installation Practices 8 2 4...

Страница 4: ...d IP67 dust tight leak proof and water tight to 1 meter Figure 1 1 FS17X Detector FS17X Connections The Model FS17X uses an eight 8 conductor Standard Cable or an optional eight 8 conductor Cable with...

Страница 5: ...Lens 4 0 mA 0 6 mA Normal Safe no Fault no Fire 20 0 mA 0 6 mA Fireball or Fire ALARM 20 0 mA 0 6 mA Fire ALARM or Verified Fire ALARM Cable Eight 8 Conductor 24 AWG or fourteen 14 Conductor 24 AWG M...

Страница 6: ...M current 2 11 W Multiple Detector output options for a variety of industrial applications Up to 32 unique digital communication addresses when RS 485 communication is used Optional RS 485 output avai...

Страница 7: ...Physical obstructions between a fire and the Detector may cause the fire to be undetected 4 The rugged stable and calibrated Polypropylene Swivel Mount SM17 is designed specifically for the FS17X Det...

Страница 8: ...Response Fireball Relay COM COMmon Fire Verification Relay COM COMmon Current Sinking 4 20mA Orange Fire ALARM Relay N O Normally Open Fire ALARM Relay N O Normally Open Fire ALARM Relay N O Normally...

Страница 9: ...RS 485 Quick Response Fireball Relay COM COMmon Fire Verification Relay COM COMmon Current Sinking 4 20mA Red Fire ALARM Relay N O Normally Open Fire ALARM Relay N O Normally Open Fire ALARM Relay N...

Страница 10: ...nal A Blue Fire ALARM Relay Terminal B Brown White Fire ALARM Relay Terminal A loop through Blue White Fire ALARM Relay Terminal B loop through Yellow Fire ALERT Relay Terminal A Orange Fire ALERT Rel...

Страница 11: ...ockwise circular motion signifying the microprocessors are successfully checking out the sensors and electronics in the Detector Module 2 4 Start Up and Commissioning ATTENTION FSX Power Up After the...

Страница 12: ...ensuring all the system wiring and cabling and system control panel s are properly installed Additionally using an external test lamp eliminates the following Detector conditions 1 The fire or flame...

Страница 13: ...ding its pushbutton While watching the red ALARM LED on the face of the Detector slowly move the Test Lamp s boresight to ensure the Detector receives its full intensity UNOTE Practicing this techniqu...

Страница 14: ...isible Band and NearBand IR are used primarily to further discriminate against non fire false alarm sources As with all Fire Sentry Corporation Detectors the Model FS17X Detector senses radiant energy...

Страница 15: ...s every 10 seconds See Figure 3 1 for the location of the Blue LED Normal Operation is defined as the Detector with 24 Vdc applied and no ALARM or Fault conditions are present Flashes LED Status 1 Blu...

Страница 16: ...rt OR Moisture is inside of the Detector Housing Contact Fire Sentry Corporation to speak with a Technical Representative 5 Yellow High or Low Temperature Fault Less than 40 C or Greater than 60 C Zon...

Страница 17: ...ting should be performed using the correct Fire Sentry Test Lamp to ensure the integrity of the entire fire protection system see Note in Section 2 4 and Section 4 3 Clean the FS17X Detector window Ea...

Страница 18: ...time inconvenience commercial loss lost profits or savings or other incidental special or consequential damages arising out of or in connection with the use or inability to use such Product THIS WARRA...

Страница 19: ...gral Cable 8 conductor Kalrez O Ring P Phoenix 8 Pin Connector Relay Contact Fault N C Normally Energized Non Latching 1 Fire Relays N O Normally De Energized Non Latching 2 Fire Relays N O Normally D...

Страница 20: ...ength 1 3 meters 10 feet 2 6 meters 20 feet Standard 3 12 meters 40 feet 4 18 meters 60 feet 5 24 meters 80 feet F O Ring K Kalrez O Ring V Viton O Ring Standard E Relay Mode N Non Latching Standard D...

Страница 21: ...or is aimed properly that its view of the fire scene has not been blocked by something such as a newly installed pipe or duct storage box parked vehicle etc and its ALARM outputs are functioning prope...

Страница 22: ...v F Copyright 2012 All Rights Reserved Page 19 4 4 Drawings 4 4 1 Outline and Dimensions Figure 4 3 Outline Dimesional Drawing for Model FS17X Figure 4 4 Outline Dimesional Drawing for SM17 Swivel Mou...

Страница 23: ...ill Energize during ALARM conditions 3 Fault relay contacts shown with no electrical power applied During normal operation and with no Fault this relay will De Energize and the N O Normally Open conta...

Страница 24: ...normal operation and with no Fault this relay will De Energize and the N O Normally Open contacts will close 4 At the Fire Alarm or Process Panel connect a jumper between 24 Vdc Supply and 4 20mA Figu...

Страница 25: ...will Energize during ALARM conditions 3 Fault relay contacts shown with no electrical power applied During normal operation and with no Fault this relay will De Energize and the N O Normally Open con...

Страница 26: ...ring normal operation and with no Fault this relay will De Energize and the N O Normally Open contacts will close 5 At the Fire Alarm or Process Panel connect a jumper between 24 Vdc Supply and 4 20mA...

Страница 27: ...ault Relay Terminal A contact to B during Normal Operation Purple Fault Relay Terminal B contact to A during Normal Operation Brown Fire Alarm Relay Terminal A Blue Fire Alarm Relay Terminal B Brown w...

Страница 28: ...Fire Verification 1 5 11 Fireball 1 2 5 FireBusII 3 5 11 12 FS17X G 5 11 FS17X R 11 FS17X S 5 11 FSIM 10 H Hazardous Location s 1 High Sensitivity 2 I Input Voltage Range 2 Installation 4 7 Introducti...

Страница 29: ...Copyright 2012 All Rights Reserved Page 26 INDEX continued T Technical Specifications 2 Test Lamp 17 TL 1055X 7 9 13 17 TL 2055X 7 9 13 17 Tubing 15 16 Twin Microprocessors 3 V Verified Fire 2 VIS 2 V...

Отзывы: