Fire Sentry FS17X Скачать руководство пользователя страница 1

 

____________________________________________________________________________________________________________________ 

 

Fire Sentry Corporation 

Document No. 6178-007 - Rev. F 

©

 Copyright 2012 

All Rights Reserved 

 

Fire Sentry Corporation 

 

23311 La Palma Avenue  
Yorba Linda, California 92887 

 

 

Telephone: 714-694-2700 

Fax: 714-694-2701 

www.firesentry.com 

 
 

FS17X WideBand IR

TM

 

Multi-Spectral Infrared Electro-Optical 

Digital WideBand IR Sensor 

Radiant Energy Fire and Flame Detector 

 

FSX

P

TM

P

 

Fire and Flame Detectors 

 

MODEL FS17X

TM

 

  

 

Installation Guide 

and

 

Operating Manual 

 

Содержание FS17X

Страница 1: ...t 2012 All Rights Reserved Fire Sentry Corporation 23311 La Palma Avenue Yorba Linda California 92887 Telephone 714 694 2700 Fax 714 694 2701 www firesentry com FS17X WideBand IRTM Multi Spectral Infr...

Страница 2: ...ns such as FS2 FS2X FS2X FS3 FS3X FS3X FS4 FS4X FS4X FS5 FS5X FS5X FS6 FS6X FS6X FS7 FS7X FS7X FS8 FS8X FS8X FS9 FS9X FS9X FS10X FS10X FS11 FS11X FS11X FS12 FS12X FS12X FS14 FS14X FS14X FS15 FS15X FS1...

Страница 3: ...pecifications 2 1 2 5 Area Classification 2 1 3 Features Benefits 3 1 4 Applications 3 SECTION 2 INSTALLATION 4 2 1 Mounting Instructions 4 2 2 Detector Connections 5 2 3 Installation Practices 8 2 4...

Страница 4: ...d IP67 dust tight leak proof and water tight to 1 meter Figure 1 1 FS17X Detector FS17X Connections The Model FS17X uses an eight 8 conductor Standard Cable or an optional eight 8 conductor Cable with...

Страница 5: ...Lens 4 0 mA 0 6 mA Normal Safe no Fault no Fire 20 0 mA 0 6 mA Fireball or Fire ALARM 20 0 mA 0 6 mA Fire ALARM or Verified Fire ALARM Cable Eight 8 Conductor 24 AWG or fourteen 14 Conductor 24 AWG M...

Страница 6: ...M current 2 11 W Multiple Detector output options for a variety of industrial applications Up to 32 unique digital communication addresses when RS 485 communication is used Optional RS 485 output avai...

Страница 7: ...Physical obstructions between a fire and the Detector may cause the fire to be undetected 4 The rugged stable and calibrated Polypropylene Swivel Mount SM17 is designed specifically for the FS17X Det...

Страница 8: ...Response Fireball Relay COM COMmon Fire Verification Relay COM COMmon Current Sinking 4 20mA Orange Fire ALARM Relay N O Normally Open Fire ALARM Relay N O Normally Open Fire ALARM Relay N O Normally...

Страница 9: ...RS 485 Quick Response Fireball Relay COM COMmon Fire Verification Relay COM COMmon Current Sinking 4 20mA Red Fire ALARM Relay N O Normally Open Fire ALARM Relay N O Normally Open Fire ALARM Relay N...

Страница 10: ...nal A Blue Fire ALARM Relay Terminal B Brown White Fire ALARM Relay Terminal A loop through Blue White Fire ALARM Relay Terminal B loop through Yellow Fire ALERT Relay Terminal A Orange Fire ALERT Rel...

Страница 11: ...ockwise circular motion signifying the microprocessors are successfully checking out the sensors and electronics in the Detector Module 2 4 Start Up and Commissioning ATTENTION FSX Power Up After the...

Страница 12: ...ensuring all the system wiring and cabling and system control panel s are properly installed Additionally using an external test lamp eliminates the following Detector conditions 1 The fire or flame...

Страница 13: ...ding its pushbutton While watching the red ALARM LED on the face of the Detector slowly move the Test Lamp s boresight to ensure the Detector receives its full intensity UNOTE Practicing this techniqu...

Страница 14: ...isible Band and NearBand IR are used primarily to further discriminate against non fire false alarm sources As with all Fire Sentry Corporation Detectors the Model FS17X Detector senses radiant energy...

Страница 15: ...s every 10 seconds See Figure 3 1 for the location of the Blue LED Normal Operation is defined as the Detector with 24 Vdc applied and no ALARM or Fault conditions are present Flashes LED Status 1 Blu...

Страница 16: ...rt OR Moisture is inside of the Detector Housing Contact Fire Sentry Corporation to speak with a Technical Representative 5 Yellow High or Low Temperature Fault Less than 40 C or Greater than 60 C Zon...

Страница 17: ...ting should be performed using the correct Fire Sentry Test Lamp to ensure the integrity of the entire fire protection system see Note in Section 2 4 and Section 4 3 Clean the FS17X Detector window Ea...

Страница 18: ...time inconvenience commercial loss lost profits or savings or other incidental special or consequential damages arising out of or in connection with the use or inability to use such Product THIS WARRA...

Страница 19: ...gral Cable 8 conductor Kalrez O Ring P Phoenix 8 Pin Connector Relay Contact Fault N C Normally Energized Non Latching 1 Fire Relays N O Normally De Energized Non Latching 2 Fire Relays N O Normally D...

Страница 20: ...ength 1 3 meters 10 feet 2 6 meters 20 feet Standard 3 12 meters 40 feet 4 18 meters 60 feet 5 24 meters 80 feet F O Ring K Kalrez O Ring V Viton O Ring Standard E Relay Mode N Non Latching Standard D...

Страница 21: ...or is aimed properly that its view of the fire scene has not been blocked by something such as a newly installed pipe or duct storage box parked vehicle etc and its ALARM outputs are functioning prope...

Страница 22: ...v F Copyright 2012 All Rights Reserved Page 19 4 4 Drawings 4 4 1 Outline and Dimensions Figure 4 3 Outline Dimesional Drawing for Model FS17X Figure 4 4 Outline Dimesional Drawing for SM17 Swivel Mou...

Страница 23: ...ill Energize during ALARM conditions 3 Fault relay contacts shown with no electrical power applied During normal operation and with no Fault this relay will De Energize and the N O Normally Open conta...

Страница 24: ...normal operation and with no Fault this relay will De Energize and the N O Normally Open contacts will close 4 At the Fire Alarm or Process Panel connect a jumper between 24 Vdc Supply and 4 20mA Figu...

Страница 25: ...will Energize during ALARM conditions 3 Fault relay contacts shown with no electrical power applied During normal operation and with no Fault this relay will De Energize and the N O Normally Open con...

Страница 26: ...ring normal operation and with no Fault this relay will De Energize and the N O Normally Open contacts will close 5 At the Fire Alarm or Process Panel connect a jumper between 24 Vdc Supply and 4 20mA...

Страница 27: ...ault Relay Terminal A contact to B during Normal Operation Purple Fault Relay Terminal B contact to A during Normal Operation Brown Fire Alarm Relay Terminal A Blue Fire Alarm Relay Terminal B Brown w...

Страница 28: ...Fire Verification 1 5 11 Fireball 1 2 5 FireBusII 3 5 11 12 FS17X G 5 11 FS17X R 11 FS17X S 5 11 FSIM 10 H Hazardous Location s 1 High Sensitivity 2 I Input Voltage Range 2 Installation 4 7 Introducti...

Страница 29: ...Copyright 2012 All Rights Reserved Page 26 INDEX continued T Technical Specifications 2 Test Lamp 17 TL 1055X 7 9 13 17 TL 2055X 7 9 13 17 Tubing 15 16 Twin Microprocessors 3 V Verified Fire 2 VIS 2 V...

Отзывы: