Panel Operation
System points will be displayed and can be referred to as follows:
Description
Syntax
Comments
ON BOARD
AZF’S
2 A
ZF’S ON TERMINATION BOARD
AZF #1
0.1.Z1
Ring 0 Module 1, zone 1
AZF #2
0.1.Z2
Ring 0 Module 1, zone 2
On Board Relays
8 Relays on termination Board
Relay 1 to 8 on FIM
0.4.O1 to 0.4.O8
Ring 0 Module 4, output 1
Ring 0 Module 4, output 8
Distributed Field Modules
Up to 100 modules
AZF
1.1.Z1
8 AZF points per AZM8module
Din
1.1.I1
3 Din Per Fan Control Module
Dout
1.1.O1
4 Dout Per AZM-8
3 Dout Per Fan Control Module
Annunciator
Up to 50 Annunciators
Inputs
1.101.I1
16 Din per 16AT, 24 Din Per SCS-8
Outputs
1.101.O1
32 Dout Per 16AT, 24 Dout Per SCS-8, 32
Dout Per ACM32A
Analog Addressable Devices
Up to 10 Loops
Detectors
L1D1
159 Detectors Per Loop
Modules
L1M1
159 Modules Per Loop
Virtual Points
VPn
n can range up to 1000
Network Points
NPn
n can range up to 1000
Expansion Relays
XRn
n can range up to 64
System Parameters
Common Alarm
CA
Common Fault
CF
Common Isolate
CI
Battery Fault
BF
Charger Fault
CL
Mains On
MO
Ext. Bell Isolated
BI
Warning System Isolated
WI
AFP-2800/2802 Manual
– P/N DOC-01-011
23
Содержание AFP-2800
Страница 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...
Страница 143: ...Appendix 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E F FR RM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 143...
Страница 144: ...Appendix 9 9 1 13 3 5 5 C CO ON NT TR RO OL L M MO OD DU UL LE E F FC CM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 144...
Страница 145: ...Appendix 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E F FZ ZM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 145...
Страница 156: ...Notes...
Страница 157: ......
Страница 158: ......