Programming
Example 3:
Isolating Z1 on Node 2 using a ACM-16at (module 101) on Node 1.
On Node 1
NP10 = 1.101.I1;
- NP10 on node 1 follows the state of the first push button on ACM-16at
1.101.O1 = N2.NP1;
- First LED on ACM-16at follows the state of Z1 on node 2 using N2.NP1
1.101.O2 = N2.NP2;
- Second LED on ACM-16at follows the isolated state of Z1 on N2 using N2.NP2
On Node 2
NP1 = SZ1;
- De-isolated state of Z1 on Node 2 transmitted to network using NP1
NP2 = IZ1;
- Isolated state of Z1 on Node 2 transmitted to network using NP2
IS
OLATE GROUP “ISOLM.1” TRIGGER = “N1.NP10” POINTS TO ISOLATE = “Z1;”
Pressing ACM-16at button on N1 will isolate Z1 on N2 and the state of Z1 on N2 is displayed on ACM-16at on N1.
8
8
.
.
2
2
.
.
1
1
S
S
P
P
E
E
C
C
I
I
A
A
L
L
N
N
E
E
T
T
P
P
O
O
I
I
N
N
T
T
S
S
NP1000
On V5.02 and above firmware if NP1000 is active, the panel will be forced to operate in night mode and stays in
night mode as long as NP1000 is active. This feature allows the programmer to use scripting for switching
between day/night modes.
NP900 to NP999
Network points 900 to 999 can be used to switch Acclimate detector(s) between normal and heat only operation.
Up to 99 individual detector lists can be switched using NP900 through NP999. If a network point between 900
and 999 is used as an isolate group trigger, the list of points associated with that isolate group will be switched to
sensitivity 9 (heat only for Acclimates) instead of the points being isolated. This functionality enables the
programmer to use scripting for switching specific groups of Acclimate detectors to heat only mode as required.
Note that the sensitivity of non Acclimate detectors in the list will also be set to 9 which means that they will still
alarm due to smoke. Ensure that all detectors in the list are Acclimates to ensure there are no unwanted alarms
due to smoke.
Example:
NP950 = 1.101.I1;
- NP950 follows the state of the first push button on ACM-16at
1.101.O1 = L1D1 OR L1D2;
- First LED on ACM-16at follows the alarm state of Acclimates
1.101.O2 = IVP950;
- Second LED on ACM-16at shows the operation mode of Acclimates
VP950 = ;
- This VP does not require a script and should be labelled to indicate the
OPERATION MODE OF THE ACCLIMATE DETECTORS. E.G.
“Z1 HEAT ONLY MODE”
ISOLATE
GROUP “ISOLM.1” TRIGGER = “NP950” POINTS TO ISOLATE = “L1D1 OR L1D2;”
IS
OLATE GROUP “ISOLM.2” TRIGGER = “1.101.I1” POINTS TO ISOLATE = “VP950;”
In the above example, the user can change the operation mode of Acclimate detectors by pressing the first button
on an ACM-16at at address 101. Note that a second isolate group is also used to isolate a VP (VP950 in this
case) to indicate the operation mode of Acclimates. The trigger of the second isolate group cannot be NP900 or
above.
Pressing the ACM-16at button for a second time will change the detector sensitivities back to their original
settings and remove VP950 from the isolate list.
Note:
If NZ mode has been selected in global options, NP996 to NP999 are reserved for special functions as
described in NZ supplement to this manual.
NPxxx cannot be programmed as ISOLM trigger through the keypad. Use PCI for programming.
Points to isolate must be a list of detectors and cannot include zones.
AFP-2800/2802 Manual
– P/N DOC-01-011
94
Содержание AFP-2800
Страница 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...
Страница 143: ...Appendix 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E F FR RM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 143...
Страница 144: ...Appendix 9 9 1 13 3 5 5 C CO ON NT TR RO OL L M MO OD DU UL LE E F FC CM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 144...
Страница 145: ...Appendix 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E F FZ ZM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 145...
Страница 156: ...Notes...
Страница 157: ......
Страница 158: ......