Appendix
9.3.2.3 E
VENT
S
OUNDER
Switch 1 of DIP switch SW1 will enable the buzzer for alarms.
Switch 2 of DIP switch SW1 will enable the buzzer for faults.
Switch 7 of DIP switch SW1 will enable the RS232 port on the LCD80 for programming.
(Note: Activation of this switch prevents the LCD80 from communicating with the FIP.)
Switch 8 of DIP switch SW1 will select terminal mode (OFF) or annunciator mode (ON)
If the buzzer is enabled, pressing the
“MUTE” BUTTON WILL SILENCE THE BUZZER UNTIL A NEW EVENT IS RECEIVED.
9.3.2.4 D
ISPLAY
The LCD Display is made up of 4 lines of 20 characters each. Events are displayed as:
Line 1
Line 2
Line 3
Comms Indicator
Point
Message
Number
Number
In the above example, the FIP has activated Point 6 on the LCD80. It is the first of 5 points which are active. The
COMMS INDICATOR
“SPINS” WHEN MESSAGES ARE being received by the LCD80.
In this example: The FIP has activated Point 12 on the LCD80.
It is the only point active.
9.3.2.5 S
PECIAL
M
ESSAGES
There are no active points on the panel programmed to
display on the LCD-80.
This messages flashes: The LCD80 has not been polled by
the CPU in over 10 seconds
100
EAST WING
NORTH
CORRIDOR
* Pt 6 Msg 1 of 5
Total Messages
EAST WING
SOUTH
CORRIDOR
* Pt 12 Msg 1 of 1
NO ACTIVE POINTS
COMMS FAILURE
AFP-2800/2802 Manual
– P/N DOC-01-011
Содержание AFP-2800
Страница 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...
Страница 143: ...Appendix 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E F FR RM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 143...
Страница 144: ...Appendix 9 9 1 13 3 5 5 C CO ON NT TR RO OL L M MO OD DU UL LE E F FC CM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 144...
Страница 145: ...Appendix 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E F FZ ZM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 145...
Страница 156: ...Notes...
Страница 157: ......
Страница 158: ......