Panel Operation
7.3.7.6
S
ERVICE
M
ENU
–
G
LOBAL
–
P
RINT
This page displays system global printer port parameters that can be toggled. The default states are shown below
on the left, while the toggled states are shown on the right.
Default Condition
Toggled Condition
DAY MODE
DAY MODE
20 JULY 2002 14:44:37
20 JULY 2002 14:44:37
SELECT A FUNCTION:
SELECT A FUNCTION:
EVENT PRINTING IS DISABLED
EVENT PRINTING IS ENABLED
ALARM ONLY EVENT PRINTING IS DISABLED
ALARM ONLY EVENT PRINTING IS ENABLED
ZONE EVENT PRINTING IS ENABLED
ZONE EVENT PRINTING IS DISABLED
HEARTBEAT CHARACTER PRINTING IS DISABLED
HEARTBEAT CHARACTER PRINTING IS ENABLED
PRINT FORMAT IS SET TO DEFAULT
PRINT FORMAT IS SET TO NFS2-3030
UP
DOWN
TOGGLE
MENU
UP
DOWN
TOGGLE
MENU
Actions:
•
Use the
UP
and
DOWN
buttons to scroll through options and then use the
TOGGLE
button to select the
toggle the highlighted option. Changes are instant.
Explanation of Global Configuration Options:
Item
Description
Event Printing
Determines if the panel should print events to the printer port.
Alarm Only Printing
This setting determines if the panel should only print alarm events or all events.
Zone Event Printing
This setting determines if the panel should print zone events as well as single
point events. If this option is enabled, the panel will print two events for a single
alarm condition (zone alarm and point alarm).
Heartbeat Character
Enable this option to print a Carriage Return character every 10 seconds. This
feature can be used to monitor the panel and communications link by a remote
system such as a BMS.
Printing Format
Determines the panel printer port output format. Default setting should be used
unless instructed by Notifier technicians. The non default format is the same as
the Notifier NFS2-3030 fire panel format and should only be used in conjunction
with the Fieldserver MODBUS gateway. The NFS2-3030 format does not print all
events and should not be used as the standard printing format.
AFP-2800/2802 Manual
– P/N DOC-01-011
80
SYSTEM CONFIGURATION
A = 0
F = 0
I = 0
N = 1
SYSTEM CONFIGURATION
A = 0
F = 0
I = 0
N = 1
Содержание AFP-2800
Страница 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...
Страница 143: ...Appendix 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E F FR RM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 143...
Страница 144: ...Appendix 9 9 1 13 3 5 5 C CO ON NT TR RO OL L M MO OD DU UL LE E F FC CM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 144...
Страница 145: ...Appendix 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E F FZ ZM M 1 1 AFP 2800 2802 Manual P N DOC 01 011 145...
Страница 156: ...Notes...
Страница 157: ......
Страница 158: ......