background image

WARNING:

 This equipment generates, uses, and can radiate radio frequency

energy and if not installed and used in accordance with the instruction manual, may

cause interference to radio communications. It has been tested and found to comply

with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC

Rules, which is designed to provide reasonable protection against such interference

when operated in a commercial environment. Operation of this equipment in a

residential area is likely to cause interference, in which case the user will be required

to correct the interference at his own expense.

Installation Precautions 

 

-   Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING 

Several different sources of power can be connected to the fire alarm

control panel.

  Disconnect all sources of power before servicing.  Control unit and

associated equipment may be damaged by removing and/or inserting cards,

modules, or interconnecting cables while the unit is energized.  Do not attempt to

install, service, or operate this unit until this manual is read and understood.

CAUTION - 

System Reacceptance Test after Software Changes:

     To ensure

proper system operation, this product must be tested in accordance with NFPA 72-

1993 Chapter 7 after any programming operation or change in site-specific software.

Reacceptance testing is required after any change, addition or deletion of system

components, or after any modification, repair or adjustment to system hardware or

wiring.

All components, circuits, system operations, or software functions known to be

affected by a change must be 100% tested.  In addition, to ensure that other

operations are not inadvertently affected, at least 10% of initiating devices that are

not directly affected by the change, up to a maximum of 50 devices, must also be

tested and proper system operation verified.

This system  

meets NFPA requirements for operation at 0-49

O

 C/32-120

O

 F

and at a relative humidity of 85% RH (non-condensing) at 30

C/86

O

 F.

However, the useful life of the system's standby batteries and the electronic

components may be adversely affected by extreme temperature ranges and

humidity.  Therefore, it is recommended that this system and its peripherals be

installed in an environment with a nominal room temperature of 15-27

O

 C/60-80

O

F.

Verify that wire sizes are adequate

 for all initiating and indicating device loops.

Most devices cannot tolerate more than a 10% I.R. drop from the specified device

voltage.

Like all solid state electronic devices,

 this system may operate erratically or can

be damaged when subjected to lightning induced transients.  Although no system is

completely immune from lightning transients and interferences, proper grounding will

reduce susceptibility.

 Overhead or outside aerial wiring is not recommended, due to

an increased susceptibility to nearby lightning strikes.

  Consult with the Technical

Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries

 prior to removing or inserting circuit boards.

Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing, reaming, or punching

of the enclosure. When possible, make all cable entries from the sides or rear.

Before making modifications, verify that they will not interfere with battery,

transformer, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.  Over tightening may damage

threads, resulting in reduced terminal contact pressure and difficulty with screw

terminal removal.

This system 

contains static-sensitive components.  Always ground yourself with a

proper wrist strap before handling any circuits so that static charges are removed

from the body.  Use static suppressive packaging to protect electronic assemblies

removed from the unit.

Follow the instructions

 in the installation, operating, and programming manuals.

These instructions must be followed to avoid damage to the control panel and

associated equipment. FACP operation and reliability depend upon proper

installation.

Fire Alarm System Limitations

While installing a fire alarm system may make lower insurance

rates possible, it is not a substitute for fire insurance!

An automatic fire alarm system

 - typically made up of smoke detectors, heat

detectors, manual pull stations, audible warning devices, and a fire alarm control

with remote notification capability can provide early warning of a developing fire.

Such a system, however, does not assure protection against property damage or

loss of life resulting from a fire.

Any fire alarm system

 may fail for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot reach the detectors such

as in chimneys, in walls, or roofs, or on the other side of closed doors.  Smoke

detectors also may not sense a fire on another level or floor of a building.  A second

floor detector, for example, may not sense a first floor or basement fire.  Further-

more, all types of smoke detectors - both ionization and photoelectric types, have

sensing limitations.  No type of smoke detector can sense every kind of fire caused

by carelessness and safety hazards like smoking in bed, violent explosions,

escaping gas, improper storage of flammable materials, overloaded electrical

circuits, children playing with matches, or arson.

IMPORTANT! 

 Smoke detectors  

must be installed in the same room as the

control panel and in rooms used by the system for the connection of alarm

transmission wiring, communications, signaling, and/or power.

  If detectors are

not so located, a developing fire may damage the alarm system, crippling its

ability to report a fire.

Audible warning devices

 such as bells  may not alert people if these devices are

located on the other side of closed or partly open doors or are located on another

floor of a building.

A fire alarm system

 will not operate without any electrical power.  If AC power fails,

the system will operate from standby batteries only for a specified time.

Rate-of-Rise heat detectors

 may be subject to reduced sensitivity over time.  For

this reason, the rate-of-rise feature of each detector should be tested at least once

per year by a qualified fire protection specialist.

Equipment used in the system

 may not be technically compatible with the control.

It is essential to use only equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a premise to a central

monitoring station may be out of service or temporarily disabled.

The most common cause

 of fire alarm malfunctions, however, is inadequate

maintenance.  All devices and system wiring should be tested and maintained by

professional fire alarm installers following written procedures supplied with each

device.  System inspection and testing should be scheduled monthly or as required

by National and/or local fire codes. Adequate written records of all inspections should

be kept.

FCC Warning

Canadian Requirements

This digital apparatus does not exceed the Class A limits for radiation noise

emissions from digital apparatus set out in the Radio Interference Regulations of the

Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radioelectriques depassant les

limites applicables aux appareils numeriques de la classe A prescrites dans le

Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-

tions du Canada.

Technical Publishing

        Document PRECAULG.PM6  12/31/96

Содержание MP-12

Страница 1: ...12 Clintonville Road Northford CT 06472 MP 12 24 Fire Alarm Control Panel Instruction Manual P N 15440 G ECN 96 200 Document 15440 6 6 96 Rev G...

Страница 2: ...yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the uni...

Страница 3: ...Notification Appliance Circuits 6 External Device Power 6 Battery Charger 6 Optional Modules 7 Section Four Installation Instructions 8 PC Board Removal 8 Optional Module Installation 8 PC Board Inst...

Страница 4: ...be used to notify a remote station or initiate a supplementary control function Standard Features A trouble circuit which monitors the following fault conditions Open detector loop s Low battery volta...

Страница 5: ...AC The green LED is on when the control panel is operating from the AC power source Yellow and green LEDs both flash to indicate below normal line voltage brown out An extinguished green LED indicates...

Страница 6: ...ting devices per zone 40 mA 10 mA Main Notification Appliance bell Circuits Activation By any zone alarm Disconnect By DISABLE switch Operation Style Y Class B Notification Appliances Use polarized UL...

Страница 7: ...udible and visual trouble signals Remote Station Type MP 12 12 VDC polarity reversal MP 24 24 VDC polarity reversal Internal Resistance of Remote Station Output MP 12 112 ohms MP 24 660 ohms Ripple Vo...

Страница 8: ...oard Cabinet and Dress Panel Optional Module Installation If an optional module is required mount it to the main printed circuit board as follows Refer to Figure 3 1 for location information Remove th...

Страница 9: ...on the system door and mark the dry contacts used as non power limited circuits Note 1 Indicates non trouble state Note 2 All contacts rated 3 A 120 VAC 30VDC Note 3 For wiring refer to UL power limi...

Страница 10: ...ng for non power limited circuits and the upper knockout for power limited circuits Module shown connected to non power limited circuit Module shown connected to power limited circuit Field Wiring All...

Страница 11: ...e End of Line Resistor ELR from the control panel and install on terminals of the last initiating device Four Wire Smoke Detectors Power for four wire smoke detectors may be obtained from terminals 5...

Страница 12: ...tral and 2 to a separate protected circuit coming directly from the line side of the main power feed to the building No other equipment may be connected to the fire alarm power circuit Wire must run c...

Страница 13: ...n Appliances sound and alarm LED lights Reset system Repeat for each zone 2 Momentarily activate the following switches one at a time and check for a trouble signal RESET DISABLE 3 Depress the TROUBLE...

Страница 14: ...determine as soon as possible if the problem is internal to the panel or in the external circuits Spare components known to be good are essential to fast efficient troubleshooting Follow the step by s...

Страница 15: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 15...

Страница 16: ...43 A 0 050 A 0 056 A 1 The table shows the maximum current available for the operation of external power consuming devices connected to the control panel for different capacity standby batteries 2 Pow...

Страница 17: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 17 NOTES...

Страница 18: ...MP12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 18 NOTES...

Страница 19: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 19 NOTES...

Страница 20: ...g constitutes the only warranty made by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in al...

Отзывы: