MP12/24 Fire Alarm Control Panel    Document 15440:G    6/6/96

10

Figure 4.4: Typical wiring diagram for side knockouts

UL Power Limited Wiring Requirements
Power limited and non-power limited circuit wiring must remain separated in the cabinet.  All power limited
circuit wiring must remain at least 0.25" away from any non-power limited circuit wiring.  Furthermore, all
power limited circuit wiring and non-power limited circuit wiring must enter and exit the cabinet through differ-
ent knockouts and/or conduits.  Create knockouts if necessary.

• For side knockouts, place the wire ties as shown in Figure 4.4.

• Use a lower knockout to run the wiring for non-power limited circuits and the upper knockout for

power limited circuits.

Module shown connected to

non power-limited circuit.

Module shown connected to

power-limited circuit.

Field Wiring

All field wiring connections are made to the screw
type terminal blocks, located along the edges of the
PC boards, as shown in wiring diagrams. Wiring
should be in accordance with National and/or Local
Codes for fire alarm systems. Use knockouts
provided on back and side of cabinet.

Figure 4.3:  Main PC Board Wiring Diagram

Ground

Neutral

To the ground stud located on the cabinet
next to the transformer assembly.

Hot

No connection

End-of-Line Resistor –
mount after the last device.

4.7K ohms (24V system)
2.2K ohms (12V system)
.

End-of-Line Resistor
(10K ohms) – mount
after the last device.

AC Power Input

Power Limited circuit

Power Limited circuit

Содержание MP-12

Страница 1: ...12 Clintonville Road Northford CT 06472 MP 12 24 Fire Alarm Control Panel Instruction Manual P N 15440 G ECN 96 200 Document 15440 6 6 96 Rev G...

Страница 2: ...yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the uni...

Страница 3: ...Notification Appliance Circuits 6 External Device Power 6 Battery Charger 6 Optional Modules 7 Section Four Installation Instructions 8 PC Board Removal 8 Optional Module Installation 8 PC Board Inst...

Страница 4: ...be used to notify a remote station or initiate a supplementary control function Standard Features A trouble circuit which monitors the following fault conditions Open detector loop s Low battery volta...

Страница 5: ...AC The green LED is on when the control panel is operating from the AC power source Yellow and green LEDs both flash to indicate below normal line voltage brown out An extinguished green LED indicates...

Страница 6: ...ting devices per zone 40 mA 10 mA Main Notification Appliance bell Circuits Activation By any zone alarm Disconnect By DISABLE switch Operation Style Y Class B Notification Appliances Use polarized UL...

Страница 7: ...udible and visual trouble signals Remote Station Type MP 12 12 VDC polarity reversal MP 24 24 VDC polarity reversal Internal Resistance of Remote Station Output MP 12 112 ohms MP 24 660 ohms Ripple Vo...

Страница 8: ...oard Cabinet and Dress Panel Optional Module Installation If an optional module is required mount it to the main printed circuit board as follows Refer to Figure 3 1 for location information Remove th...

Страница 9: ...on the system door and mark the dry contacts used as non power limited circuits Note 1 Indicates non trouble state Note 2 All contacts rated 3 A 120 VAC 30VDC Note 3 For wiring refer to UL power limi...

Страница 10: ...ng for non power limited circuits and the upper knockout for power limited circuits Module shown connected to non power limited circuit Module shown connected to power limited circuit Field Wiring All...

Страница 11: ...e End of Line Resistor ELR from the control panel and install on terminals of the last initiating device Four Wire Smoke Detectors Power for four wire smoke detectors may be obtained from terminals 5...

Страница 12: ...tral and 2 to a separate protected circuit coming directly from the line side of the main power feed to the building No other equipment may be connected to the fire alarm power circuit Wire must run c...

Страница 13: ...n Appliances sound and alarm LED lights Reset system Repeat for each zone 2 Momentarily activate the following switches one at a time and check for a trouble signal RESET DISABLE 3 Depress the TROUBLE...

Страница 14: ...determine as soon as possible if the problem is internal to the panel or in the external circuits Spare components known to be good are essential to fast efficient troubleshooting Follow the step by s...

Страница 15: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 15...

Страница 16: ...43 A 0 050 A 0 056 A 1 The table shows the maximum current available for the operation of external power consuming devices connected to the control panel for different capacity standby batteries 2 Pow...

Страница 17: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 17 NOTES...

Страница 18: ...MP12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 18 NOTES...

Страница 19: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 19 NOTES...

Страница 20: ...g constitutes the only warranty made by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in al...

Отзывы: