MP12/24 Fire Alarm Control Panel Document 15440:G 6/6/96
10
Figure 4.4: Typical wiring diagram for side knockouts
UL Power Limited Wiring Requirements
Power limited and non-power limited circuit wiring must remain separated in the cabinet. All power limited
circuit wiring must remain at least 0.25" away from any non-power limited circuit wiring. Furthermore, all
power limited circuit wiring and non-power limited circuit wiring must enter and exit the cabinet through differ-
ent knockouts and/or conduits. Create knockouts if necessary.
• For side knockouts, place the wire ties as shown in Figure 4.4.
• Use a lower knockout to run the wiring for non-power limited circuits and the upper knockout for
power limited circuits.
Module shown connected to
non power-limited circuit.
Module shown connected to
power-limited circuit.
Field Wiring
All field wiring connections are made to the screw
type terminal blocks, located along the edges of the
PC boards, as shown in wiring diagrams. Wiring
should be in accordance with National and/or Local
Codes for fire alarm systems. Use knockouts
provided on back and side of cabinet.
Figure 4.3: Main PC Board Wiring Diagram
Ground
Neutral
To the ground stud located on the cabinet
next to the transformer assembly.
Hot
No connection
End-of-Line Resistor –
mount after the last device.
4.7K ohms (24V system)
2.2K ohms (12V system)
.
End-of-Line Resistor
(10K ohms) – mount
after the last device.
AC Power Input
Power Limited circuit
Power Limited circuit
Содержание MP-12
Страница 15: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 15...
Страница 17: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 17 NOTES...
Страница 18: ...MP12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 18 NOTES...
Страница 19: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 19 NOTES...