MP-12/24 Fire Alarm Control Panel Document 15440:G 6/6/96
9
Figure 4.2: Optional Modules
MP-TR
MP-AC
MP-AT
Connect to compatible UL Listed polarity sensitive remote
station receiver, Fire•Lite RS-82 or equivalent. Output
signal: MP-12, 9 to 14 VDC; MP-24, 18 to 28 VDC.
Note 1: For wiring refer to UL power limited requirements.
Note 2: The MP-TRT module does not comply with the
requirement for separate trouble/alarm signal
transmission.
Note 3: This circuit is suitable to leave the building.
Note 4: This output is power-limited.
Trouble output
contacts.
Alarm output
contacts.
NO
NC
Pole
Pole
NC*
NO*
Two sets
Form-C
alarm
contacts.
Rating: 3 A
resistive,
120 VAC/
30 VDC.
NO #2
NC #2
Pole #2
Pole #1
NO #1
NC #1
Note 1: For wiring refer to UL power limited requirements.
Note 2: Both sets of contacts must either be connected to
a non-power limited or a power limited circuit. Sets
of contacts cannot be mixed.
Note 3: Refer to the Protected Premises Unit label
(located on the system door) and mark the dry
contacts used as non power-limited circuits.
Note 1: *Indicates non-trouble state.
Note 2: All contacts rated 3 A, 120 VAC/30VDC.
Note 3: For wiring refer to UL power limited requirements.
Note 4: Both sets of contacts must be connected to a
non power-limited or a power limited circuit. Sets
of contacts cannot be mixed.
Note 5: Refer to the Protected Premises Unit label
(located on the system door) and mark the dry
contacts used as non power-limited circuits.
Remote Station
disconnect switch
+
-
Reverse Polarity
Remote Station output.
Polarity shown is for
normal standby state.
Polarity reverses on
alarm.
Connect to compatible UL Listed polarity sensitive remote
station receiver, Fire•Lite RS-82 or equivalent. Output
signal: MP-12, 9 to 14 VDC; MP-24, 18 to 28 VDC.
Note 1: For wiring refer to UL power limited requirements.
Note 2: This circuit is suitable to leave the building.
Note 3: This output is power-limited.
MP-TRT
Remote Station
disconnect switch
Reverse Polarity
Remote Station output.
Polarity shown is for
normal standby state.
Polarity reverses on
alarm. Output signal is
0 volts during non-
alarm trouble condition.
+
-
Содержание MP-12
Страница 15: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 15...
Страница 17: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 17 NOTES...
Страница 18: ...MP12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 18 NOTES...
Страница 19: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 19 NOTES...