MP12/24 Fire Alarm Control Panel    Document 15440:G    6/6/96

6

Section Three:

Technical Specifications

All specifications are typical characteristics measured under nominal conditions at 25° C, unless otherwise specified.

System Power Requirements

MP-12/24 Operating voltage: 120 VAC, 60 Hz (standard).
MP-12/24 Current Draw: 0.5 A (maximum).
MP-12/24E Operating voltage:  220/240 VAC, 50/60 Hz
MP-12/24E Current Draw: 0.250 A (maximum).
Standby battery:

Voltage: (MP-12) 12 VDC; (MP-24) 24 VDC
Capacity: 2.5 to 7.0 AH (dependent on external loading).

Detection Loop

Operation:  Style B (Class B).
Voltage: (MP-12)  8.6 to 12.2 VDC, ripple 0.65 Vp-p. (MP-24) 18 to 26.2 VDC, ripple 2.0 Vp-p.
Current required to ensure alarm: 20 mA (minimum)
Short circuit current: 40 mA - 10 mA
Supervision current: 5 mA
ELR: (MP-12) 2.2 K, 0.5 W;  (MP-24) 4.7K, 0.5 W
Max resistance per side: 100 ohms.
Max total zone resistance: 200 ohms.

Two-wire Smoke Detectors

Head voltage, standby: MP-12, 11 VDC;  MP-24, 23 VDC.
Total standby head current per zone: 2 mA peak
Minimum head current to ensure alarm: 20 mA
Maximum alarm current supplied to initiating devices, per zone: 40 mA - 10 mA.

Main Notification Appliance (bell) Circuits

Activation: By any zone alarm
Disconnect: By DISABLE switch
Operation: Style Y (Class B).
Notification Appliances:  Use  polarized, UL  Listed,  Notification Appliances with a minimum rated voltage
range of 9-15 VDC on MP-12 and 18-30 VDC on MP-24. Refer to the Fire•Lite Device Compatibility Docu-
ment for a listing of compatible devices.
Nominal output voltage: (MP-12) 12 VDC; (MP-24) 24 VDC.
Output is 

Special Purpose Power (full wave rectified DC, unregulated and unfiltered).

Output current: Total current to all external Notification Appliances cannot exceed: (MP-12) 1.0 A; (MP-24)
0.75 A.

External Device Power

Regulated DC output: Resettable power primarily for four-wire smoke detectors and/or other low power
electronic devices. Maximum current available: 100 mA
Note: Size standby battery to include external loading.
Nominal voltage: (MP-12) 12 VDC;  (MP-24) 24 VDC.

Battery Charger

Float type, turned off during alarm.
Float voltage setting: (MP-12) 13.8 VDC; (MP-24) 27.6 VDC.  Automatic current limiting.
Note:  Since battery charger is pulsed on and off, the charger output cannot be read with a voltmeter when
battery is not connected.  A typical voltmeter would read approximately 8.5 V on the MP-12 and 16.5 V on the
MP-24.

Содержание MP-12

Страница 1: ...12 Clintonville Road Northford CT 06472 MP 12 24 Fire Alarm Control Panel Instruction Manual P N 15440 G ECN 96 200 Document 15440 6 6 96 Rev G...

Страница 2: ...yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the uni...

Страница 3: ...Notification Appliance Circuits 6 External Device Power 6 Battery Charger 6 Optional Modules 7 Section Four Installation Instructions 8 PC Board Removal 8 Optional Module Installation 8 PC Board Inst...

Страница 4: ...be used to notify a remote station or initiate a supplementary control function Standard Features A trouble circuit which monitors the following fault conditions Open detector loop s Low battery volta...

Страница 5: ...AC The green LED is on when the control panel is operating from the AC power source Yellow and green LEDs both flash to indicate below normal line voltage brown out An extinguished green LED indicates...

Страница 6: ...ting devices per zone 40 mA 10 mA Main Notification Appliance bell Circuits Activation By any zone alarm Disconnect By DISABLE switch Operation Style Y Class B Notification Appliances Use polarized UL...

Страница 7: ...udible and visual trouble signals Remote Station Type MP 12 12 VDC polarity reversal MP 24 24 VDC polarity reversal Internal Resistance of Remote Station Output MP 12 112 ohms MP 24 660 ohms Ripple Vo...

Страница 8: ...oard Cabinet and Dress Panel Optional Module Installation If an optional module is required mount it to the main printed circuit board as follows Refer to Figure 3 1 for location information Remove th...

Страница 9: ...on the system door and mark the dry contacts used as non power limited circuits Note 1 Indicates non trouble state Note 2 All contacts rated 3 A 120 VAC 30VDC Note 3 For wiring refer to UL power limi...

Страница 10: ...ng for non power limited circuits and the upper knockout for power limited circuits Module shown connected to non power limited circuit Module shown connected to power limited circuit Field Wiring All...

Страница 11: ...e End of Line Resistor ELR from the control panel and install on terminals of the last initiating device Four Wire Smoke Detectors Power for four wire smoke detectors may be obtained from terminals 5...

Страница 12: ...tral and 2 to a separate protected circuit coming directly from the line side of the main power feed to the building No other equipment may be connected to the fire alarm power circuit Wire must run c...

Страница 13: ...n Appliances sound and alarm LED lights Reset system Repeat for each zone 2 Momentarily activate the following switches one at a time and check for a trouble signal RESET DISABLE 3 Depress the TROUBLE...

Страница 14: ...determine as soon as possible if the problem is internal to the panel or in the external circuits Spare components known to be good are essential to fast efficient troubleshooting Follow the step by s...

Страница 15: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 15...

Страница 16: ...43 A 0 050 A 0 056 A 1 The table shows the maximum current available for the operation of external power consuming devices connected to the control panel for different capacity standby batteries 2 Pow...

Страница 17: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 17 NOTES...

Страница 18: ...MP12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 18 NOTES...

Страница 19: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 19 NOTES...

Страница 20: ...g constitutes the only warranty made by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in al...

Отзывы: