Recording Custom Messages
Programming
3.4.3 Microphone
Messages can be recorded into the system using the onboard microphone.
1.
Enter programming mode at the main control board.
2.
Enable
Recording Mode
in the system’s message recording programming section. Refer to
3.
Press zone button 17 to record. Then press zone button 1-14 that will be the designated
message slot. The yellow zone LED will light.
4.
Press the push-to-talk (PTT) button on the microphone and speak the message.
5.
Release the PTT button on the microphone to save the message. The green LED for this
message slot will light.
6.
Press the zone button selected in step 3 to play back the recorded message.
7.
If the recorded message is not satisfactory, it can be erased (see Section 3.4.4) and re-recorded
by following these steps.
8.
Enter programming mode again and deselect
Message Record Mode.
Recording with Microphone - Example
To record into message slot 5 via the microphone:
Enter the Local Recording mode via the online programming utility. Select the
Message Record
Mode
option. The display board will light green zone 1-14 LEDs for all message slots that are
occupied.
If a message already exists in message slot 5, it must first be erased. Press zone button 24, then
zone button 5. (See Section 3.4.4) When the message has been erased, the green zone LED will
turn off.
To record the message, press zone button 17, then zone button 5. The yellow zone LED will blink.
Press the PTT button on the microphone and speak the message. Release the PTT button to save
the message. The yellow zone 5 LED will stay lit while recording. The green LED for zone button
5 will light after the recording is complete.
NOTE:
The display board will light green zone LEDs for message slots that are occupied. If a
message is already stored in that message slot, it must first be erased. See Section 3.4.4.
Содержание ECC-100
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 104: ...104 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 110: ...Cut along dotted line...
Страница 112: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com...