UL Power-limited Wiring Requirements
Installation
2.12 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" away from any nonpower-limited circuit
wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the
cabinet through different knockouts and/or conduits. A typical wiring diagram for the ECC-50/100
with two speaker circuits is shown below.
Figure 2.30 Typical Wiring Diagram for UL Power-limited Requirements
Power-limited Circuits
(Class 2)
ec
cu
lp
w
r.w
m
f
Power-limited Circuits
(Class 2)
Power-limited
Circuits
(Class 2)
AC Power
Nonpower-
limited Circuit
Power-limited
Circuits
(Class 2)
Power-limited
Circuits
(Class 2)
to batteries
nonpower-
limited circuit
Power-limited
Circuits
(Class 2)
NOTE:
Use of the 70V transformer makes all power-limited circuits Class 3.