94
Emergency Command Center Manual —
P/N LS10001-000FL-E:D 9/3/2014
Power Supply Calculations
Calculating the System Current Draw
6.3.2 How to use Table 6.2 to calculate system current draws
1.
Enter the quantity of devices in both columns.
2.
Enter the DC current draw where required. Refer to the
Fire•Lite Device Compatibility
Document
for compatible devices and their current draw.
3.
Calculate the current draws for each in both columns.
4.
Sum the total current for each column.
5.
Copy the totals from Column 1 and Column 2 to Table 6.3 on page 95.
Following are the types of current that can be entered into Table 6.2:
Calculation Column 1
- The standby current load that the audio panel must support (from
the batteries) during a non-fire alarm condition and a loss of AC power.
Calculation Column 2
- The alarm current draw that the audio panel must support (from
the batteries) during a fire alarm condition and a loss of AC power
Table 6.2 contains two columns for calculating current draws. For each column, calculate the cur-
rent and enter the total (in amps) in the bottom row. When finished, copy the totals from Calcula-
tion Column 1 and Calculation Column 2 to Table 6.3 on page 95.
Device Type
Calculation Column 1
Secondary (Battery) Power Source
Standby Current (amps)
Calculation Column 2
Secondary (Battery) Power Source
Alarm Current (amps)
Qty
X [current
draw] =
total
Qty
X [current draw]
=
total
ECC-50/100 Primary Console
(Not including speaker load)
1
X [0.272]=
0.272
1
X [0.446]=
0.446
ECC-50W-25/70V
Optional Audio Amplifier Module
1
[ ]
(1 max.)
X [0.100]=
[ ]
[ ]
(1 max.)
X [0.235]=
[ ]
ECC-CE6 Speaker Circuit Expander
[ ]
(1 max.)
X [0.020]=
[ ]
[ ]
(1 max.)
X [0.189]=
[ ]
ECC-LOC Local Operator Console
2
[ ]
X [0.085]=
[ ]
[ ]
X [0.100]=
[ ]
ECC-RM Remote Microphone
[ ]
X [0.050]=
[ ]
[ ]
X [0.064]=
[ ]
ECC-RPU Remote Page Unit
[ ]
X [0.050]=
[ ]
[ ]
X [0.068]=
[ ]
ECC-50DA, ECC-125DA, ECC-50BDA
Remote Amplifiers
3
[ ]
X [0.012]=
[ ]
[ ]
X [0.012]=
[ ]
ECC-FFT Firefighter Telephone
[ ]
X[0.120]=
[ ]
[ ]
X[0.230]=
[ ]
Speakers (50 watts maximum/amplifier)
1/4 Watt
[ ]
X[0.017]=
[ ]
1/2 Watt
[ ]
X[0.033]=
[ ]
3/4 Watt
[ ]
X[0.050]=
[ ]
1 Watt
[ ]
X[0.068]=
[ ]
2 Watts
[ ]
X[0.132]=
[ ]
Additional Current Draw from TB17 Special
Application Auxiliary Power Output
(0.5 amp maximum)
[ ]
X [ ]=
[ ]
[ ]
X [ ]=
[ ]
NAC Circuit Output (2.0 amps maximum)
[ ]
X [ ]=
[ ]
Power Supervision Relays
4
[ ]
X [0.025]=
[ ]
[ ]
X [0.025]=
[ ]
AIM-1A, RSM-1A Isolators
[ ]
X [0.0145]=
[ ]
[ ]
X [0.0145]=
[ ]
SP-SVC Volume Control
[ ]
X[0.010]=
[ ]
[ ]
X[0.010]=
[ ]
Sum each column for totals
Secondary Standby:
Secondary Alarm:
Table 6.2 System Current Draw Calculations
1 In backup configurations, the optional amplifier draws no additional current in alarm.
2 Maximum combined total of eight (8) operator interface devices.
3 Maximum combined total of eight (8) remote amplifiers.
4 Must use a compatible, UL-listed Power Supervision Relay
Содержание ECC-100
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 104: ...104 Emergency Command Center Manual P N LS10001 000FL E D 9 3 2014 Slide in Labels...
Страница 110: ...Cut along dotted line...
Страница 112: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com...