15465 Rev F 5/2/97 P/N 15465:F
46
Annunciator Present (63) Factory default is "0", no annunciator
present. Changing address 63 to a "1" means that an annunciator is in
use.
Zone 4 Function Select (64) Zone 4 is factory set at "0" to be a
Supervisory Zone. (Accepts N.O. Supervisory devices) Changing
address 64 to "1" allows Zone 4 to accept any N.O. contact device.
Note: When Address 64 is changed to "1", the messages transmitted to
the Central Stations must be changed to reflect the new setting. If
using 3+1, 4+1 or 4+2 Expanded Formats, Address 71 must be
changed to "1" and Address 159 must be changed to "1". If using 4+2
Standard Formats, Address 74 must be changed to "1" and Address 162
must be changed to "1."
Address (65) Not used.
Touchtone/Rotary Select (66) A "0" programmed in this address by
the factory triggers Touchtone dialing over both phone lines. Select
"1" for rotary dialing.
Make Break Ratio (67) Use the address only if you have chosen "1"
for address 66. The make/break ratio is factory set to "0" which is 67/
33, but may be changed to "1" which is a 62/38 ratio.
Programming Event Codes (68-243)
Tables 4.3-1 to 4.3-4 list messages or "event codes" that are sent to the
Central Station. The selections made for the Primary Number
Communication Format (address 16) and the Secondary Number
Communication Format (address 42) automatically program addresses
68-243 with factory default selections.
Any of the event codes may be changed. Consult your Central Station
prior to altering the event codes. Entering a code of "zero" will cause
the communicator to NOT transmit the message. For the 3+1, 4+1
formats or the 4+2 expanded format enter a single zero. For the 4+2
standard format enter two zeros.
Be certain to disable the reports in pairs. The pair should include both
the activation of the event and the restoral of the event. For example
to disable Zone 1 Fault Code from being transmitted, enter a '0' or '00'
for the Fault Code plus a '0' or '00' for the Zone 1 Fault Restoral Code.
The exception to this is for the 24 Hour Test Reports and the
Abnormal Test Reports.
Technical Manuals Online! - http://www.tech-man.com