15465 Rev F 5/2/97 P/N 15465:F
30
3.4 UL Power-
limited Wiring
Requirements
Power-limited and nonpower-limited circuit wiring must remain
separated in the cabinet. All power-limited circuit wiring must remain
at least 0.25" away from any nonpower-limited circuit wiring.
Furthermore, all power-limited circuit wiring and nonpower-limited
circuit wiring must enter and exit the cabinet through different
knockouts and/or conduits. A typical wiring diagram for the MS-5012
is shown below.
Power-limited Circuits
Power-limited
Circuits
Power-limited
Circuits
AC Power
Figure 3.4-1: Typical Wiring Diagram for UL Power-limited Requirements