Program Mode
42
Document #51073 Rev.A 1/19/99 P/N 51073:A
4+2 Standard and 4+2 Express Formats Secondary Central Station Event Codes
If 1, A or C is entered for address 50, the following data is automatically programmed for the Secondary Central Sta-
tion phone number event codes. Enter '00' for the Setting to disable the report to the Central Station.
TABLE 3-5:
4+2 Standard and 4+2 Express Formats - Secondary
Address
Description
Setting
229 - 230
Secondary # Input Channel 1 Active Event Code
11
231 - 232
Secondary # Input Channel 2 Active Event Code
12
233 - 234
Secondary # Input Channel 3 Active Event Code
13
235 - 236
Secondary # Input Channel 4 Active Event Code
14
237 - 238
Secondary # Input Channel 1 Fault Event Code
F1
239 - 240
Secondary # Input Channel 2 Fault Event Code
F2
241 - 242
Secondary # Input Channel 3 Fault Event Code
F3
243 - 244
Secondary # Input Channel 4 Fault Event Code
F4
245 - 246
Secondary # AC Fault Event Code
92
247 - 248
Secondary # Earth Fault Event Code
61
249 - 250
Secondary # Low Battery Fault Event Code
62
251 - 252
Secondary # No Battery Fault Event Code
63
253 - 254
Secondary # Phone Line 1 Voltage Fault Event Code
64
255 - 256
Secondary # Phone Line 2 Voltage Fault Event Code
65
257 - 258
Secondary # NAC Fault Event Code
66
259 - 260
Secondary # Phone Number 1 Communication Fault Event Code
6A
261 - 262
Secondary # Phone Number 2 Communication Fault Event Code
6B
263 - 264
Secondary # System Off Normal Fault Event Code
6F
265 - 266
Secondary # Input Channel 1 Active Restore Code
E1
267 - 268
Secondary # Input Channel 2 Active Restore Code
E2
269 - 270
Secondary # Input Channel 3 Active Restore Code
E3
271 - 272
Secondary # Input Channel 4 Active Restore Code
E4
273 - 274
Secondary # Input Channel 1 Fault Restore Code
D1
275 - 276
Secondary # Input Channel 2 Fault Restore Code
D2
277 - 278
Secondary # Input Channel 3 Fault Restore Code
D3
279 - 280
Secondary # Input Channel 4 Fault Restore Code
D4
281 - 282
Secondary # AC Voltage Fault Restore Code
93
283 - 284
Secondary # Earth Fault Restore Code
A1
285 - 286
Secondary # Low Battery Fault Restore Code
A2
287 - 288
Secondary # No Battery Fault Restore Code
A3
289 - 290
Secondary # Phone Line 1 Voltage Fault Restore Code
A4
291 - 292
Secondary # Phone Line 2 Voltage Fault Restore Code
A5
293 - 294
Secondary # NAC Fault Restore Code
A6
295 - 296
Secondary # Phone Number 1 Communication Fault Restore Code
AA
297 - 298
Secondary # Phone Number 2 Communication Fault Restore Code
AB
299 - 300
Secondary # System Off Normal Restore Code
AF
301 - 302
Secondary # System Test Message
99
303 - 304
Secondary # System Abnormal Test Message
91
305 - 306
Secondary # Upload/Download Request Code
71
307 - 308
Secondary # Upload Successful Code
72
309 - 310
Secondary # Download Successful Code
73
311 - 312
Secondary # Upload/Download Failed Code