UL Power-limited Wiring Requirements
28
Document #51073 Rev.A 1/19/99 P/N 51073:A
2.8
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any nonpower-limited circuit wiring. Furthermore, all power-limited
and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A
typical wiring diagram for the 411UDAC is shown below.
E AR TH A C -N EU A C -H OT
FIGURE 2-13:
Typical UL Power-limited Wiring Diagram
AC Power
Nonpower-limited Circuits
Power-limited Circuits
411A
ULP
W
.CDR
Note: Relay connections may be power-limited or nonpower-
limited, provided that 0.25" spacing is maintained between
conductors of power-limited and nonpower-limited circuits.