Document #51073 Rev. A 1/19/99 P/N 51073:A
65
Programming Sheets
❏
68
Input Channel 4 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel
trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi-
lenceable; '8' for process monitoring; '9' for process monitoring autoresettable.
❏
69
❏
70
❏
71
Input Channel 1 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
❏
72
❏
73
❏
74
Input Channel 2 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
❏
75
❏
76
❏
77
Input Channel 3 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
❏
78
❏
79
❏
80
Input Channel 4 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
❏
81
Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
❏
82
Make/Break Ratio for Primary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
❏
83
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
❏
84
Make/Break Ratio for Secondary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
❏
85
Output Relay #1 enable. Enter '0' to enable Relay #1; '1' to disable relay (requires optional 411RK Relay Kit).
❏
86
Output Relay #1 Function. Enter '0' for relay to activate on alarm; '1' (future use); '2' for supervisory; '3' for
supervisory autoresettable; '4' for process monitoring; '5' for process monitoring autoresettable; '6' for host panel trou-
ble; '7' for DACT trouble; '8' for total communication failure (requires optional 411RK Relay Kit).
❏
87
Output Relay #2 enable. Enter '0' to enable Relay #2; '1' to disable relay (requires optional 411RK Relay Kit).
❏
88
Output Relay #2 Function. Enter '0' for relay to activate on alarm; '1' (future use); '2' for supervisory; '3' for
supervisory autoresettable; '4' for process monitoring; '5' for process monitoring autoresettable; '6' for host panel trou-
ble; '7' for DACT trouble; '8' for total communication failure (requires optional 411RK Relay Kit).
❏
89
Reserved for future use. Leave default setting of ‘0.’
❏
90
Reserved for future use. Leave default setting of ‘0.’
❏
91
Alarm verification. Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
❏
92
Silence inhibit. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC for one minute.
❏
93
Autosilence. Enter '0' for no autosilence; '1' for 5 minute autosilence; '2' for 10 minutes; '3' for 15 minutes; '4'
for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❏
94
Restoral method. Enter '0' for Typical restoral method; '1' for Conditional Restoral Method #1; '2' for
Conditional Restoral Method #2.
❏
95
Coding, Notification Appliance Circuit. Enter ‘0’ for no coding (steady); ‘1’ for Temporal coding.
Note that when coding is selected, NAC output is not power-limited.
❏
96
Trouble Call Limit - Dialer Runaway Prevention Feature. Enter a '0' to disable this feature; '1' to enable Trou-
ble Call Limit. Factory default is '0' for disabled.
❏
97
❏
98
❏
99
❏
100
Panel Identification Number.