MANUAL PILOT FIREBOWL
Side Mounted Ignition
•
45
•
54
•
68 NL & LL Firebowl
CONNECTION
25
GENERAL SPECIFICATIONS
The firebowl must be installed on site, pressure
and leak checked by a certified gas technician
as per national and local, building, gas, fire, and
safety codes and ordinances.
The Firebowl comes supplied with a Maxitrol
525-5AL Individual low pressure appliance reg-
ulator. A ‘plain view’ emergency gas shut-off
valve, is to be supplied and installed by a cer-
tified gas technician as per national and local,
building, gas, fire, and safety codes and ordi-
nances.
BURNER & BTU SPECIFICATIONS
The burner for this appliance is assembled and
tested by:
Charles A. Hones Inc., P.O. Box 405 - 355 NY
State Route 49, Cleveland, NY 13042,
(315) 623-2124
The burner is a special, stainless steel, “Yellow
Flame” burner, and is rated at a minimum of
150,000 and a maximum of 300,000 BTU’s.
The burner is supplied with the appropriate 1/4”
brass orifice for use with either natural gas (NG)
or propane (LP), a modified 90M stainless steel
air mixer, and stainless steel pipe connections.
CONNECTION DIAMETER
The Baso Safety Valve has a 3/4” connection to
the gas source.
ORIFICE SIZES & OPERATING
PRESSURES
45” Models:
LP Maximum BTU = 150,000 w. #26 DMS
orifice @ 11” W.C. Inlet - 10” W.C. Manifold
NG Maximum BTU = 150,000 BTU w. #6
DMS orifice @ 7” W.C. Inlet - 6” W.C. Mani
-
fold
54” & 68” Models:
LP Maximum BTU = 300,000 w. #4 DMS
orifice @ 11” W.C. Inlet - 10” W.C. Manifold
NG Maximum BTU = 300,000 BTU w. #K
DMS orifice @ 7” W.C. Inlet - 6” W.C. Mani
-
fold
PLAIN SIGHT EMERGENCY SHUT-OFF
VALVE WITH REGULATOR
LEGEND
Maxitrol Regulator 325-5AL Gas Appliance
Pressure Regulator. SUPPLY PRESSURE NOT
TO EXCEED 2PSI.
T-1001 Legend Full Port 3/4” Ball Valve
‘PLAIN VIEW’ Shut Off Valve.
This valve must be installed within 10’ to 15’
of the appliance or to local code.
Off Position
On Position
1
2