K.
Parameter Table
Parameter Display
Name of Parameters
Description of Parameters
Setting Range
Pre-set
value
Scale Hi
Greatest PV value
~
100.0
Scale Lo
Lowest PV value
~
0.0
Sensor input voltage
Sensor AD voltage
Sensor Hi
Greatest voltage input
.
~
.
0.25
Sensor Lo
Lowest voltage input
.
~
.
0.1
Scale Enable
Scale enable switch
/
OFF
¾
:
Greatest PV value
:
Set PV value in Span voltage.
¾
:
Lowest PV value
:
Set PV value in Zero voltage.
PV can be re-transmitted for t-PV(Transfer PV).
¾
:
Sensor AD voltage
:
Set SCHi
、
SCLi.
¾
:
Greatest voltage input
:
Set greatest measuring voltage in Sensor input.
¾
:
Lowest voltage input
:
Set lowest measuring voltage in Sensor input.
¾
:
Input switch
:
ON/OFF voltage input in PV display
Ex. 1
:
PV value 0.0~ 100.0 corresponds to 0~10V
DC output in SUB2 terminal
Steps
:
1
、
StUP
→
SUB2 = t-PV in main menu
2
、
SCAL
→
SCH = 100.0 in main menu
3
、
SCAL
→
SCL = 0.0 in main menu
4
、
Complete setup
Ex. 2
:
0-10mV value corresponds to PV 0.0~200.0 in
Sensor output
Steps
:
1
、
Connect 0-10mV DC to PT8 in Sensor
output terminal.
2
、
SCAL
→
SCH = 200.0
3
、
SCAL
→
SCL = 0.0
4
、
Input 0V to observe SCAL
→
SEnS and input
value into SCAL
→
SCLi
5
、
Input 10mV to observe SCAL
→
SEnS and
input value into SCAL
→
SCHi
6
、
SCAL
→
SCEN = ON
7
、
Back to main menu
Input 0mV, PV = 0.0?
Input 10mV, PV = 200.0?
8
、
Complete setup
32