background image

 

¾

 

       :

Proportional Gain parameter

Can be calculated by auto tuning or adjusted manually. This 

parameter is responsible to the system deviation. When offset occurs, proportional regulator 

responds to reduce the offset.   

¾

 

       :

Integral parameter

Can be calculated by auto tuning or adjusted manually. When steady offset 

exist in a consistent temperature, Integral regulator will start compensating until offset is fixed. 

¾

 

       :

Derivative parameter

Can be calculated by auto tuning or adjusted manually. Derivative regulator 

can predict the system trend by rate of change; derivative regulator will fix the offset in advance, 

before offset happens. 

¾

 



   :

Fuzzy factor parameter. Can be calculated by auto tuning or adjusted manually. 

Fuzzy control compensates the insufficiency of PID controller and helps to reach the target based 

on the deviation and rate of change. 

Bigger Tau, more Fuzzy compensation! 

¾

 



 :

Cooling coefficient. Can be calculated by auto tuning or adjusted manually. 

Cooler proportional gain = P / Coef 

This function is used in cooling control, to tell the performance of cooler. 

¾

 



 :

Manual reset. 

When Integral i=0, and PV>SV, then MV=MArE. 

¾

 



 :

SV offset setting during Auto tuning 

When this function is set up, auto tuning will make the system to oscillate around SV + oFSt . For 

example, SV=200°C

OFST= -10°C. Auto tuning will calculate as SV+OFST=200+(-10)=190°C

to avoid over-heating. 

¾

 



   :

Hysteresis for heater on/off control. 

¾

 



 :

Hysteresis for cooler on/off control. 

During ON/OFF control, control output should be turned off when PV>SV, and turned on when 

PV<SV. To avoid frequent ON and OFF control, hysteresis can be set.  When HYS is set, 

PV>SV+HYS to turn off the control output, and turned on when PV<SV-HYS. 

¾

 



 :

Heater control cycle time(sec) 

¾

 



 :

Cooler control cycle time(sec) 

For any control output that is not in linear analog signal such as relay and 12V pulse output, signal 

output status will be ON/OFF only. For better PID result, Time Proportional is used.    For example, 

period is set to be 5 seconds and PID is 30%.  (ON)= 30%. 5*0.3=1.5 sec.  (OFF)= 70%  

5*0.7=3.5 sec. 

Control output reacts quicker as cycle time gets shorter. When mechanical contact output is used, 

please consider issue of mechanical life. 

 

8

Содержание PT-8320 Series

Страница 1: ...PT 8320 User Manual 1...

Страница 2: ...DIMENSION PANEL CUTOUT 2...

Страница 3: ...PANEL DESCRIPTION EXPLANATION FOR TERMINAL WIRING 3...

Страница 4: ...of Output Control 0 50 0 seconds Digital 0 3 digital Digital Filter 1 100 times Control Method ON OFF or PID Fuzzy Auto Tuning Input Compensation 1999 9999 Fraction Value 0 0 999 9 Setting Range 1999...

Страница 5: ...Advance setting for control Prog Ramp Soak setting ALM Alarm setting StUP Hardware construction setting EXPA Expansion function setting CoMM Communication setting LoCK Lock function SCAL Analog auxil...

Страница 6: ...e Ramp Soak control mode which means oPEr onoF or Pid Indication of the on going step 0 Ramp Soak control not starts yet SV Maintain the last SV EXPA Pend SV after patterns are completed 1 3 5 7 9 11...

Страница 7: ...er dead band Dead band of cooler 0 CT current monitor Display CT 1 Heater burnout Heater break setting 0 section of parameters are used for basic control P I D tAU CoEF parameters affect PID Fuzzy con...

Страница 8: ...n P Coef This function is used in cooling control to tell the performance of cooler Manual reset When Integral i 0 and PV SV then MV MArE SV offset setting during Auto tuning When this function is set...

Страница 9: ...ter Deactivates cooler Deactivates cooler Deactivates heater SV SV DB H SV DB C SV DB C SV SV DB H DB H 0 DB C 0 DB H 0 DB C 0 Over SV DB H deactivates heater Over SV DB H deactivates heater Under SV...

Страница 10: ...Lo Re transmit SV low value 0 section is for advanced control parameters ON OFF or PID control mode can be configured to achieve the requirement Under SV PV mode press 3 times of MOD button it is for...

Страница 11: ...e manipulate value to be used in determining whether the control output should be strong or weak in order to constantly calculating the deviation of stability and prediction The built in Fuzzy control...

Страница 12: ...ction LBA heater burnout temperature difference Set LBA burnout temperature difference When system is being heated and temperature increase is less than the temperature difference within LBA time cont...

Страница 13: ...rol function Every pattern can perform 8 steps of temperature control Via link pattern 64 steps of temperature control can be performed Press MOD 4 times under SV PV mode sub menu can be selected unde...

Страница 14: ...k 2 followed by Pattern 1 Link 1 followed by Pattern 2 Signal output procedure signal output setup r1 Temperature increase 1 s1 Temperature holding 1 r2 Temperature increase 2 s2 Temperature holding 2...

Страница 15: ...Alarm position 4 0 0 Hysteresis 4 Hysteresis 4 sec 0 0 Delay Time 4 Delay Time 4 0 Style 4 Style 4 Sty1 There are 4 sets of alarm parameter setting designed to fit different application condition In...

Страница 16: ...esis 3 setup Delay time 3 setup sec Style 3 selection Please refer to StyL alarm style description Position 4 setup Hysteresis 4 setup Delay time 4 setup sec Style 4 selection Please refer to StyL ala...

Страница 17: ...g alarm sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 7...

Страница 18: ...m sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 50 DY1...

Страница 19: ...sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 50 DY1 s...

Страница 20: ...sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 70 DY1 s...

Страница 21: ...ignal output Alarm output off When PV SV POS1 HYS1 or PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 5...

Страница 22: ...ignal output Alarm output off When PV SV POS1 HYS1or PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 50...

Страница 23: ...alarm sends out signal output Alarm output off When PV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 10 POS1 60 HYS1 5 DY1 5 When PV 60 DY1...

Страница 24: ...Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 10 DY1 starts timing When DY1 finishes timing alarm sends out signal output When PV 15 alarm output stops 6 9 SErr Signal Error...

Страница 25: ...utput transmission Selectable output types Sub 2 control alarm output transmission Selectable output types Heater control output Cooler control output Alarm output to be performed with ALM for detail...

Страница 26: ...se set LV 2 tr H 100 LV 2 tr L 0 Aux 1 input Aux 2 input Aux 3 input Aux 4 input Offer different signal input including remote SV value RSP remote Event current transformer and CT input Remote SV valu...

Страница 27: ...de Switch on LV 0 Prog rSt Switch off LV 0 Prog rUn Switch on LV 0 Prog HoLd Switch off LV 0 Prog Retrieve Hold original setting Switch on LV 0 AdV on Output direction 1 Forward reverse Output directi...

Страница 28: ...ulation At H value is preset to be 0 5 System will be heated to PV 0 5 and cooled to PV 0 5 during Auto Tune Power on setup This mode is designed for 8 patterns Program mode It can set Continue Reset...

Страница 29: ...V SV main menu auto return Display will automatically returned to PV SV main menu when there is no new setup for time input Setup range is oFF 10 20 30 40 50 60 Default oFF Not return to PV SV automat...

Страница 30: ...the address of control unit Selection for Baud Rate communication 600 Baud rate 600 1200 Baud rate 1200 2400 Baud rate 2400 4800 Baud rate 4800 9600 Baud rate 9600 19200 Baud rate 19200 38400 Baud ra...

Страница 31: ...BEL Lock selection LB00 Through LAbe parameter setting it is adjust the main menu selectable and good for use friendly avoid the possibility mistake in setting function LB00 LB01 LB02 LB03 LB04 PV SV...

Страница 32: ...t greatest measuring voltage in Sensor input Lowest voltage input Set lowest measuring voltage in Sensor input Input switch ON OFF voltage input in PV display Ex 1 PV value 0 0 100 0 corresponds to 0...

Страница 33: ...value in Zero voltage Sensor AD Voltage To calibrate zero span voltage Set Span Voltage Set greatest voltage output for AD Set Zero Voltage Set lowest voltage value for AD Ex Set input of 0 10vdc in...

Страница 34: ...se refer to CT input module in the right 1 Connect CT transformer to PT8 AUX1 2 Select Ct under StUP AUX1 in main menu 3 Select HbA under StUP SUB1 in main menu 4 Observe AD voltage exceeds 0 100v whe...

Страница 35: ...After calibration voltage and resistance can be measured accurately Sub menu 1 PAS Input correct password to enter password 12 2 0mV Calibrate 0mv input 3 50mV Calibrate 50mV input 4 r100 Calibrate 10...

Страница 36: ...4 Set calibrator output 0mV 15 Press to enter Aic 0mv to edit Press until value is stable then press to confirm 16 Set calibrator output 50mV 17 Press to enter Aic 50mv to edit Press until value is st...

Страница 37: ...of Parameters Setting Range Default Manual operation Display PV value Heater MV Control heater output manipulate value 0 Cooler MV Control cooler output manipulate value 0 Display PV value Control he...

Отзывы: