6.5



 Out-Range Alarm 

Alarm output on 

When PV<=SV+POS1 or PV<=SV-POS1, DY1   

starts timing. 

When DY1 finishes timing, alarm sends out   

signal output. 

 

Alarm output off 

When PV>=SV+POS1+HYS1 or   

PV<=SV+POS1-HYS1, alarm output stops. 

 

Ex.

 

PV= present value 

SV= set value 

POS1= Alarm set point 

DY1= Alarm delay time 

 

SV=60

 POS1=10

   

HYS1=5

 DY1=5; 

When PV<=50 or PV>=70, DY1 starts timing. 

When DY1 finishes timing, alarm   

sends out signal output. 

 

When PV>=55 or PV<=65, alarm output stops. 

 

 

 

 

 

 

 

 

21

Содержание PT-8320 Series

Страница 1: ...PT 8320 User Manual 1...

Страница 2: ...DIMENSION PANEL CUTOUT 2...

Страница 3: ...PANEL DESCRIPTION EXPLANATION FOR TERMINAL WIRING 3...

Страница 4: ...of Output Control 0 50 0 seconds Digital 0 3 digital Digital Filter 1 100 times Control Method ON OFF or PID Fuzzy Auto Tuning Input Compensation 1999 9999 Fraction Value 0 0 999 9 Setting Range 1999...

Страница 5: ...Advance setting for control Prog Ramp Soak setting ALM Alarm setting StUP Hardware construction setting EXPA Expansion function setting CoMM Communication setting LoCK Lock function SCAL Analog auxil...

Страница 6: ...e Ramp Soak control mode which means oPEr onoF or Pid Indication of the on going step 0 Ramp Soak control not starts yet SV Maintain the last SV EXPA Pend SV after patterns are completed 1 3 5 7 9 11...

Страница 7: ...er dead band Dead band of cooler 0 CT current monitor Display CT 1 Heater burnout Heater break setting 0 section of parameters are used for basic control P I D tAU CoEF parameters affect PID Fuzzy con...

Страница 8: ...n P Coef This function is used in cooling control to tell the performance of cooler Manual reset When Integral i 0 and PV SV then MV MArE SV offset setting during Auto tuning When this function is set...

Страница 9: ...ter Deactivates cooler Deactivates cooler Deactivates heater SV SV DB H SV DB C SV DB C SV SV DB H DB H 0 DB C 0 DB H 0 DB C 0 Over SV DB H deactivates heater Over SV DB H deactivates heater Under SV...

Страница 10: ...Lo Re transmit SV low value 0 section is for advanced control parameters ON OFF or PID control mode can be configured to achieve the requirement Under SV PV mode press 3 times of MOD button it is for...

Страница 11: ...e manipulate value to be used in determining whether the control output should be strong or weak in order to constantly calculating the deviation of stability and prediction The built in Fuzzy control...

Страница 12: ...ction LBA heater burnout temperature difference Set LBA burnout temperature difference When system is being heated and temperature increase is less than the temperature difference within LBA time cont...

Страница 13: ...rol function Every pattern can perform 8 steps of temperature control Via link pattern 64 steps of temperature control can be performed Press MOD 4 times under SV PV mode sub menu can be selected unde...

Страница 14: ...k 2 followed by Pattern 1 Link 1 followed by Pattern 2 Signal output procedure signal output setup r1 Temperature increase 1 s1 Temperature holding 1 r2 Temperature increase 2 s2 Temperature holding 2...

Страница 15: ...Alarm position 4 0 0 Hysteresis 4 Hysteresis 4 sec 0 0 Delay Time 4 Delay Time 4 0 Style 4 Style 4 Sty1 There are 4 sets of alarm parameter setting designed to fit different application condition In...

Страница 16: ...esis 3 setup Delay time 3 setup sec Style 3 selection Please refer to StyL alarm style description Position 4 setup Hysteresis 4 setup Delay time 4 setup sec Style 4 selection Please refer to StyL ala...

Страница 17: ...g alarm sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 7...

Страница 18: ...m sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 50 DY1...

Страница 19: ...sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 50 DY1 s...

Страница 20: ...sends out signal output Alarm output off When PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 70 DY1 s...

Страница 21: ...ignal output Alarm output off When PV SV POS1 HYS1 or PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 5...

Страница 22: ...ignal output Alarm output off When PV SV POS1 HYS1or PV SV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 50...

Страница 23: ...alarm sends out signal output Alarm output off When PV POS1 HYS1 alarm output stops Ex PV present value SV set value POS1 Alarm set point DY1 Alarm delay time SV 10 POS1 60 HYS1 5 DY1 5 When PV 60 DY1...

Страница 24: ...Alarm set point DY1 Alarm delay time SV 60 POS1 10 HYS1 5 DY1 5 When PV 10 DY1 starts timing When DY1 finishes timing alarm sends out signal output When PV 15 alarm output stops 6 9 SErr Signal Error...

Страница 25: ...utput transmission Selectable output types Sub 2 control alarm output transmission Selectable output types Heater control output Cooler control output Alarm output to be performed with ALM for detail...

Страница 26: ...se set LV 2 tr H 100 LV 2 tr L 0 Aux 1 input Aux 2 input Aux 3 input Aux 4 input Offer different signal input including remote SV value RSP remote Event current transformer and CT input Remote SV valu...

Страница 27: ...de Switch on LV 0 Prog rSt Switch off LV 0 Prog rUn Switch on LV 0 Prog HoLd Switch off LV 0 Prog Retrieve Hold original setting Switch on LV 0 AdV on Output direction 1 Forward reverse Output directi...

Страница 28: ...ulation At H value is preset to be 0 5 System will be heated to PV 0 5 and cooled to PV 0 5 during Auto Tune Power on setup This mode is designed for 8 patterns Program mode It can set Continue Reset...

Страница 29: ...V SV main menu auto return Display will automatically returned to PV SV main menu when there is no new setup for time input Setup range is oFF 10 20 30 40 50 60 Default oFF Not return to PV SV automat...

Страница 30: ...the address of control unit Selection for Baud Rate communication 600 Baud rate 600 1200 Baud rate 1200 2400 Baud rate 2400 4800 Baud rate 4800 9600 Baud rate 9600 19200 Baud rate 19200 38400 Baud ra...

Страница 31: ...BEL Lock selection LB00 Through LAbe parameter setting it is adjust the main menu selectable and good for use friendly avoid the possibility mistake in setting function LB00 LB01 LB02 LB03 LB04 PV SV...

Страница 32: ...t greatest measuring voltage in Sensor input Lowest voltage input Set lowest measuring voltage in Sensor input Input switch ON OFF voltage input in PV display Ex 1 PV value 0 0 100 0 corresponds to 0...

Страница 33: ...value in Zero voltage Sensor AD Voltage To calibrate zero span voltage Set Span Voltage Set greatest voltage output for AD Set Zero Voltage Set lowest voltage value for AD Ex Set input of 0 10vdc in...

Страница 34: ...se refer to CT input module in the right 1 Connect CT transformer to PT8 AUX1 2 Select Ct under StUP AUX1 in main menu 3 Select HbA under StUP SUB1 in main menu 4 Observe AD voltage exceeds 0 100v whe...

Страница 35: ...After calibration voltage and resistance can be measured accurately Sub menu 1 PAS Input correct password to enter password 12 2 0mV Calibrate 0mv input 3 50mV Calibrate 50mV input 4 r100 Calibrate 10...

Страница 36: ...4 Set calibrator output 0mV 15 Press to enter Aic 0mv to edit Press until value is stable then press to confirm 16 Set calibrator output 50mV 17 Press to enter Aic 50mv to edit Press until value is st...

Страница 37: ...of Parameters Setting Range Default Manual operation Display PV value Heater MV Control heater output manipulate value 0 Cooler MV Control cooler output manipulate value 0 Display PV value Control he...

Отзывы: