 SRP Remote Status Indicator Engineering and Commissioning Manual

 

 

12 
 

Installation and Commissioning 

Topology & Cabling 

 

All  system  wiring  should  be  installed  to  comply  with  BS  5839:  Pt  1:  2002  and  BS  7671  (wiring 
regulations) and any other standards relevant to the area or type of installation. A cable complying with 
BS 5839: Pt 1: 2002 Category 1 (cable required to operate for prolonged periods during fire conditions) 
is  required.  This  must  be  a  2-core  1.5mm

2

  screened  fire  resistant  cable  (i.e.  MICC,  FP200,  Firetuff, 

Firecell, Lifeline or equivalent).  
 
In order to protect against possible data corruption it is important to ensure the following points are 
adhered to: 

 

1.  The cable screen must be connected to the SCRN terminal for each circuit

 

at the RSI. 

 

2.  The  cable  screen  must  not  be  connected  to  earth/ground  at  any  point  other  than  the 

Control Panel (at the SCRN terminal provided). Do not connect the screen to a  metal back 
box. 

 

3.  The  cable  screen  continuity  must  be  maintained  at  every  point  of  the  circuit,  using  the 

terminals provided or a suitable connection block. 

 

4.  Do not use a 4-core cable for 24V supply and communications, due to the possibility of data 

corruption.  It  is  essential  that  two  2-core  screened  cables  are  used,  one  for  the  24V  DC 
supply and the other for communications. 

 
 
 

Maximum Cable Lengths 

The maximum total

 

cable length from the Control Panel to an RSI is 500 metres for power and 

communication

 

Up to 8 RSIs can be used but they must all be within the maximum 500 metres cable length.

 

 

The maximum cable length from the RSI to the HOLD and RELEASE switches is 100 metres. 
 
Refer to the 

“Power Supply & Connections” and “Peripheral Bus Connections” sections below for further 

details. 

 

Содержание TWINFLEX SRP

Страница 1: ...62 01 TWINFLEX SRP Fire Suppression System Remote Status Indicator RSI Suitable for TWINFLEX SRP Control Panel from V01 000 Engineering and Commissioning Manual TO BE RETAINED BY THE COMMISSIONING ENG...

Страница 2: ...ssioning should only be carried out by competent persons Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with without variation E OE TWINFLEX Mulit...

Страница 3: ...ndicator Back Board Power Supply Connections 13 Peripheral Bus Connections 14 SRP Control Panel Connector Board Peripheral Bus Connections 14 Remote Status Indicator Back Board Peripheral Bus Connecti...

Страница 4: ...Indicator Specification 25 Fire Alarm System Notice 26 To Enable the Control Panel Keys 26 To Manually Operate the Fire Alarm Sounders 26 Following a Fire Alarm Operation 26 Following a Fault Conditio...

Страница 5: ...ntee The equipment carries no warranty unless the system is installed commissioned and serviced in accordance with this manual and the relevant standards by a suitably qualified and competent person o...

Страница 6: ...el using the TWINFLEX data protocol Remote Status Indicator RSI The TWINFLEX Remote Status Indicator connects to a Control Panel and reports events that occur on the system It does not connect to any...

Страница 7: ...s or in a position that may require access panels to be removed Do not locate the RSI where extremes of temperature or humidity may occur i e close to a heat source or where there is any possibility o...

Страница 8: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 8...

Страница 9: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 9...

Страница 10: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 10 Physical Dimensions...

Страница 11: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 11 General Assembly Ribbon Cable Connection Fixing Front Panel To Back Box...

Страница 12: ...RSI 2 The cable screen must not be connected to earth ground at any point other than the Control Panel at the SCRN terminal provided Do not connect the screen to a metal back box 3 The cable screen co...

Страница 13: ...0V SCRN Screen Screen When powering an RSI from the panel the extra current will reduce the battery backup run time and has to be allowed for in the battery calculations NOTE A jumper wire MUST be ins...

Страница 14: ...e second RSI and so on The peripheral bus must not be spurred from one central point SRP Control Panel Connector Board Peripheral Bus Connections There are two sets of peripheral bus connections on th...

Страница 15: ...the RELEASE operation The maximum cable length from the EXT SWITCHES connector on the RSI Back Board to the SW1 HOLD and SW2 RELEASE switches is 100 metres The Activation Resistor may be either 680 or...

Страница 16: ...orts an RSI Missing fault The RSI must be supervised to be fully functional The Home Screen on the RSI indicates that it is supervised by displaying a check mark next in the upper right corner of the...

Страница 17: ...Control Panel The RSI displays the same Home Screen message as the SRP Control Panel lines 2 and 3 If the Home Screen is modified on the SRP Control Panel the Home Screen on the RSI gets updated autom...

Страница 18: ...users and responsible persons have been trained properly See the End User Training section below Fault finding If the Date and Time do not update on the RSI and are not in sync with the SRP Control Pa...

Страница 19: ...l Panel has reached the release state and release outputs have been activated Continuous The Control Panel has reached the release state and release outputs have been activated and sounders have been...

Страница 20: ...T EVENTS 5 ALL EVENTS 1 FIRE EVENTS 2 FAULT EVENTS The main Fire Alarm Controls may be enabled by turning the key switch to the controls enabled position to go from access level 1 to access level 2 Th...

Страница 21: ...the Controls Enabled light which shows the level selected as follows RSI Access Level Summary Access Level ACCESS Description Home Screen Display upper right x RSI Address Controls Enabled LED Key Ope...

Страница 22: ...ng the enter or ESC button when in Access Level 1 will show the VIEW CURRENT EVENTS Menu with an arrow pointing to the events to be selected for viewing Fire Fault Disable Panel or All events The menu...

Страница 23: ...HT The TEST LEDS option causes the panel LEDs to toggle on off and will illuminate to ensure correct operation The test will count down and return to the TEST MODES menu screen The TEST KEYPAD option...

Страница 24: ...TUS option displays the current RSI address that is set by the DIL switches A0 to A2 located next to the buzzer The display will time out and return to the STATUS VERSION screen The BUZZER STATUS opti...

Страница 25: ...r storage in an accessible and known location in order that the responsible person and the service engineer may keep information records up to date A single page user instruction sheet is included at...

Страница 26: ...nel keys turn the key switch off When disabled the Enabled LED should then be extinguished The red FIRE LED will illuminate The fire alarms and the internal buzzer will operate as programmed Take appr...

Страница 27: ...___________________________________________________________________________ ADDRESS ______________________________________________________________________ For Service Phone _________________ During Wo...

Страница 28: ...rette smoke etc then clear the smoke from the area and press reset on the Control Panel If the alarm state does not re annunciate then no further action is required If the fire alarms in the communal...

Страница 29: ...TWINFLEX SRP Remote Status Indicator Engineering and Commissioning Manual 29 Engineers Notes...

Страница 30: ...inguishing systems in and around buildings Technical Support Contact your distributor for technical support on this product Do not call the Fike Safety Technology technical support department unless y...

Отзывы: