BASE ADDRESS

TO NEXT DEVICE 

STATUS

INDICATORS

   

  +

   

  +

+0

+1

IDC

ADDRESS

   

  +

   

  +

+2

+3

IDC

ADDRESS

   

  +

   

  +

+4

+5

IDC

ADDRESS

SLC

   

  +

   

  +

+

+

FROM PANEL OR

PREVIOUS DEVICE

3.9K EOL

RESISTOR

(INCLUDED)

CONNECT MODULES TO 

LISTED COMPATIBLE 

CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS B IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

+

+

T6

T5

DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE  MODULE.

INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

(–)

(+)

IN

OUT

   

  +

   

  +

EXTERNAL SUPPL

Y

POWER-LIMITED

AND SUPERVISED

POWER TO THE NEXT INTERFACE

MODULE MUST BE EXTERNALLY

SWITCHED TO RESET THE DETECTORS.

A FIK-M500R RELAY CONTROL MODULE CAN 

BE USED TO SWITCH POWER FROM A 

STANDARD POWER SUPPLY. SEE FIGURE 10.

0

1

2

3

4

5 6

7 8 9

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

FIGURE 5. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B

C0812-04

1.   To use a common power sup-

ply between multiple FIK-CZ-6 
modules, connect a long power 
supply jumper from T5 or T6 
to T5 or T6 on the adjacent 
FIK-CZ-6 module. 

BASE ADDRESS

TO NEXT DEVICE

STATUS

INDICATORS

   

  +

   

  +

+0

+1

IDC

ADDRESS

   

  +

   

  +

+2

+3

IDC

ADDRESS

   

  +

   

  +

+4

+5

IDC

ADDRESS

SLC

   

  +

   

  +

+

+

FROM PANEL OR

PREVIOUS DEVICE

CONNECT MODULES TO LISTED COMPATIBLE 

HONEYWELL FARENHYT SERIES  CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.

SEE PANEL INSTRUCTION MANUAL

FOR WIRE REQUIREMENTS.

CLASS A IDC (TYPICAL)

A/B SELECT

A/B SELECT

DISABLE 1

DISABLE 2

+

+

IDC 2

IDC 3

(–)

(+)

POWER TO THE NEXT INTERFACE

MODULE MUST BE EXTERNALLY

SWITCHED TO RESET THE DETECTORS.

AN FRM-1 RELAY CONTROL MODULE CAN BE

USED TO SWITCH POWER FROM A

STANDARD POWER SUPPLY. SEE FIGURE 10.

T6

T5

IN

OUT

   

  +

   

  +

EXTERNAL SUPPL

Y

POWER-LIMITED

AND SUPERVISED

DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE. INSTALL 

DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

0

1

2

3

4

5 6

7 8 9

0

1

2

3

4

5 6

7 8 9

10

11

12

13

14

15

FIGURE 6. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A

C0813-04

1.   To select Class A, remove the 

two shunts from the “A/B se-
lect” positions.

2.   To use a common power sup-

ply between multiple FIK-CZ-6 
modules, connect a long power 
supply jumper from T5 or T6 
to T5 or T6 on the adjacent 
FIK-CZ-6 module. 

FIGURE 7. RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

TO NEXT 

DEVICE

RELAY CONTROL 

MODULE

CONNECT MODULES TO LISTED 

COMPATIBLE CONTROL PANELS ONLY

FROM PANEL 

OR PREVIOUS 

DEVICE

POWER LIMITED DC 

POWER SUPPLY, 

LISTED FOR FIRE 

PROTECTION WITH 

BATTERY BACKUP

C0248-02

  

I56-6896-000 

 

 1/15/2021

Содержание FIK-CZ-6

Страница 1: ...this module shall be connected to a compatible Fike system control panel list available from Fike A list of compatible two wire System Sensor Smoke detectors for use with the FIK CZ 6 is available on the Fike website COMPONENTS The following is a description of the FIK CZ 6 mounting framework One or two FIK CZ 6 modules can be installed in a FIK BB 2 cabinet FIGURE 1 FIK BB 2 CABINET 0 1 2 3 4 5 6...

Страница 2: ...ass B operation if the shunt for Address Dis able is placed on two and the base switch is set to 28 the modules will be assigned to 28 29 30 and 31 while disabling the highest two positions NOTE Place unused shunts on single pin to store on board for future use WIRING NOTES Power limited circuits must employ type FPL FPLR or FPLP cable as required by Article 760 of the NEC All wiring must be in ac...

Страница 3: ... DEVICE CONNECT MODULES TO LISTED COMPATIBLE HONEYWELL FARENHYT SERIES CONTROL PANELS ONLY SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS CLASS A IDC TYPICAL A B SELECT A B SELECT DISABLE 1 DISABLE 2 IDC 2 IDC 3 POWER TO THE NEXT INTERFACE MODULE MUST BE EXTERNALLY SWITCHED TO RESET THE DETECTORS AN FRM 1 RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM ...

Страница 4: ...st harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or te...

Отзывы: