background image

FIGURE 4B. INSTALLATION OF FIK-CZ-6 MODULE IN FRONT CHASSIS 

POSITION

 

2

3

1

 

 C0226-00

Step 1:   Insert the bottom edge of the FIK-CZ-6 module down into a front slot 

of the chassis.

Step 2:   Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the 1¼" (31.75mm) standoffs installed on the 
rear module.

Step 3:  Align two 4-40 screws with the two standoffs and tighten.
Step 4:   Address and wire the modules according to the instructions in this 

manual.

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations.
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.   All wiring to the FIK-CZ-6 is done via terminal blocks. In order to prop-

erly make electrical connections strip approximately ¼" of insulation 
from the end of wire, sliding the bare end of the wire under the clamping 
plate screw. 

3.    Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module between 01 and 94 (or 01 
and 154 for panels that support 159 addresses).

In Class B operation, the remaining modules are automatically assigned to the 
next five higher addresses. For example, if the base address switch is set to 28, 
the next five modules will be addressed to 29, 30, 31, 32 and 33.

The module is shipped in Class B position, remove shunts for Class A. When 
operating in Class A, alternate modules are paired together (+0/+1, +2/+3, 
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the 
modules while 29, 31 and 33 are available to be used for other modules on the 
SLC. For Class A and B operation, DO NOT set the lowest address above 94 
(or 154 for panels which support 159 addresses), as the other modules will be 
assigned to nonexistent addresses.

NOTE: The FIK-CZ-6 must have power cycled for shunt changes to take effect.

4.   A shunt is provided to disable a maximum of two unused modules in 

Class B operation and Class A operation. Modules are disabled from the 
highest address and work downward. If two modules are disabled, the 
lowest four addresses will be functional, while the highest two will be 
disabled. For example, in Class B operation, if the shunt for Address Dis-
able is placed on “two” and the base switch is set to 28, the modules will 
be assigned to 28, 29, 30 and 31 while disabling the highest two positions.

NOTE:  Place unused shunts on single pin to store on board for future use.

WIRING NOTES

•  Power-limited circuits must employ type FPL, FPLR, or FPLP cable as 

required by Article 760 of the NEC.

•  All wiring must be in accordance with the NEC, NFPA 72 and all other 

applicable codes and standards. All external power supplies must be 
power limited with battery back-up. All external power supplies and 
detectors must be UL listed for fire protection signaling applications.

PROGRAMMING

The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.

FIGURE 2. TYPICAL MOUNTING HOLE LOCATIONS

 

BACKBOX
MOUNTING
HOLES

 C0235-00

2.  Module Installation

There are two methods for installing a module in the rear position of a chas-
sis. Method one is for installation of a rear module only, when no module will 
be installed in front of it. Refer to Figure 3 for instructions. Method two is for 
installation of a rear module when another module will be installed in the 
chassis position in front of it. Refer to Figures 4a and 4b for method two. All 
necessary screws and standoffs are supplied with the modules.

FIGURE 3. INSTALLATION OF REAR MODULE ONLY, METHOD ONE

 

2

3

1

   C0237-00

Step 1:   Insert the bottom of the FIK-CZ-6 module down into a rear slot on the 

chassis. 

Step 2:   Carefully swing the upper edge of the board back towards the back of 

the chassis until it touches the two standoffs.

Step 3:  Align two 4-40 screws with the two standoffs and tighten.
Step 4:   Address and wire the modules according to the instructions in this 

manual.

The steps in Figures 4a and 4b describe and illustrate module installation 
when the rear chassis position and the position in front of it will be filled. 
Front position installation is possible only if the rear position is filled with a 
module. 

FIGURE 4A. INSTALLATION OF FIK-CZ-6 MODULE IN A REAR CHASSIS 

POSITION, METHOD TWO

 

1

 C0225-00

Step 1:   Insert the bottom edge of the FIK-CZ-6 module down into a rear slot 

of the chassis.

Step 2:   Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the short standoff attached to the chassis.

Step 3:  Align the long standoff with the short standoff and tighten. 

  

I56-6896-000 

 

 1/15/2021

Содержание FIK-CZ-6

Страница 1: ...this module shall be connected to a compatible Fike system control panel list available from Fike A list of compatible two wire System Sensor Smoke detectors for use with the FIK CZ 6 is available on the Fike website COMPONENTS The following is a description of the FIK CZ 6 mounting framework One or two FIK CZ 6 modules can be installed in a FIK BB 2 cabinet FIGURE 1 FIK BB 2 CABINET 0 1 2 3 4 5 6...

Страница 2: ...ass B operation if the shunt for Address Dis able is placed on two and the base switch is set to 28 the modules will be assigned to 28 29 30 and 31 while disabling the highest two positions NOTE Place unused shunts on single pin to store on board for future use WIRING NOTES Power limited circuits must employ type FPL FPLR or FPLP cable as required by Article 760 of the NEC All wiring must be in ac...

Страница 3: ... DEVICE CONNECT MODULES TO LISTED COMPATIBLE HONEYWELL FARENHYT SERIES CONTROL PANELS ONLY SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS CLASS A IDC TYPICAL A B SELECT A B SELECT DISABLE 1 DISABLE 2 IDC 2 IDC 3 POWER TO THE NEXT INTERFACE MODULE MUST BE EXTERNALLY SWITCHED TO RESET THE DETECTORS AN FRM 1 RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM ...

Страница 4: ...st harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or te...

Отзывы: