Troubleshooting
151086
7-3
7.2
System Messages
Table 7.2-1 shows the messages that could appear on the LCD of the model 10-2257 annunciator.
If you have a problem that is not covered here, contact Technical Support at 816-229-3405 for
assistance.
Note: When step programming mode is in use and the 10-2257 annunciator powers up, the LCD displays messages
that describe conditions currently in effect.
Table 7-3: Explanations of Display Messages
10-2257 Message
Reason for Display
AC LOW
AC power has been lost. Check connection to AC power source.
ALARM ZONE 1-4
An alarm condition exists in the indicated zone.
BAD EEPROM
10-2257 buzzer goes on and off.
Most likely cause is a bad EEPROM chip, which is not an installer-serviceable
part. Contact Technical Support if you need to arrange for a warranty exchange.
Line 2: CALLING COMPUTER
System is calling remote computer (for up- or downloading).
Line 2: REPORTING
The system is reporting to the central station.
REPORTING
An event is being reported to the central station.
SYSTEM NORMAL
No trouble, alarm, or other condition exists.
TIME?
The 10-2256 is in Time Set mode.
TROUBLE (line 1)
TROUBLE ZONE # (line 2)
Sprinkler supervisory trouble.
TROUBLE (ZONE 1-4)
A trouble condition exists in the indicated zone. If you need help locating the
trouble, refer to Section 7.1 for information about zone troubleshooting mode
(mode 25).
TROUBLE DIALER
After making the programmed number of attempts, the dialer has not been able to
communicate with the central station. (This is a dialer failed condition.)
TROUBLE LINE 1
A trouble condition exists on phone line 1.
TROUBLE LINE 2
A trouble condition exists on phone line 2.
TRY AGAIN
A keystroke error has been made. Press
and enter the correct
keystrokes.
CLEAR
OBSOLETE
Содержание 10-2256
Страница 1: ...DIGITAL ALARM COMMUNICATOR PRODUCT MANUAL Manual P N 06 160 Rev 1 04 01 10 2256 O B S O L E T E ...
Страница 8: ...Model 10 2256 Fire Slave Communicator Installation Manual 1 4 151086 O B S O L E T E ...
Страница 24: ...Model 10 2256 Fire Slave Communicator Installation Manual 3 14 151086 O B S O L E T E ...
Страница 28: ...Model 10 2256 Fire Slave Communicator Installation Manual 4 4 151086 O B S O L E T E ...
Страница 44: ...Model 10 2256 Fire Slave Communicator Installation Manual 6 6 151086 O B S O L E T E ...
Страница 48: ...Model 10 2256 Fire Slave Communicator Installation Manual 7 4 151086 O B S O L E T E ...