Model 10-2256 Fire Slave Communicator Installation Manual
7-2
151086
Table 7-1 explains how to use Mode 25. Note that while you are using Mode 25, all alarms and
troubles are disabled to allow you to trip channels (zones), adjust wiring, and so on.
The readings shown in Table 7.1-2 are typical for normal conditions.
Table 7-1: Using Mode 25
To
Press
Enter Mode 25
[Installer's Code]
Select the channel (or zone) you want to
troubleshoot
1.
(You must be in Mode 25.)
2. Channel #
= Channel 1 (or Zone 1)
= Channel 2 (or Zone 2)
= Channel 3 (or Zone 3)
= Channel 4 (or Zone 4)
= AC monitoring function
Exit Mode 25
Table 7-2: Typical Mode 25 Values
Supervised Channel (or Zone) Input
Mode 25 Values All Values are Approximate
Normal Conditions
Active (Tripped)
Trouble
Valid Range Typical Value Valid Range Typical Value
Active High
8 to 11
9
21 to 31
27
0 to 7
or
12 to 20
Active Low
8 to 11
or
21 to 31
9
0 to 7
1
12 to 20
Contact Closure
8 to 11
9
0 to 7
1
12 to 31
Non-Supervised Channel (or Zone) Input
Active High
0 to 20
16
21 to 31
27
Active Low
12 to 31
16
0 to 11
1
Contact Closure
12 to 31
16
0 to 11
1
Active High AC Monitoring
0 to 20
16
21 to 31
27
Active Low AC Monitoring
8 to 31
16
0 to 7
1
Direct AC Monitoring
0 to 11
1
12 to 31
16
2 5 ENTER
ENTER
ENTER
1
2
3
4
5
STEP
STEP CLEAR CLEAR
OBSOLETE
Содержание 10-2256
Страница 1: ...DIGITAL ALARM COMMUNICATOR PRODUCT MANUAL Manual P N 06 160 Rev 1 04 01 10 2256 O B S O L E T E ...
Страница 8: ...Model 10 2256 Fire Slave Communicator Installation Manual 1 4 151086 O B S O L E T E ...
Страница 24: ...Model 10 2256 Fire Slave Communicator Installation Manual 3 14 151086 O B S O L E T E ...
Страница 28: ...Model 10 2256 Fire Slave Communicator Installation Manual 4 4 151086 O B S O L E T E ...
Страница 44: ...Model 10 2256 Fire Slave Communicator Installation Manual 6 6 151086 O B S O L E T E ...
Страница 48: ...Model 10 2256 Fire Slave Communicator Installation Manual 7 4 151086 O B S O L E T E ...